English
Language : 

G2AK-232A-DC24 Datasheet, PDF (1/8 Pages) Omron Electronics LLC – Magnetic Latching Version of G2A Ideal for Sequence Control
Latching Relay
G2AK
Magnetic Latching Version of G2A Ideal for
Sequence Control
• Double-winding latch system with continuous rating.
• Terminals pulled from the respective junctions between the
built-in diodes and set and reset coils allow the built-in diodes to
be externally connected for coil surge absorption.
• Excellent vibration/shock resistance with minimal secular
decrease in latching power.
• Easy monitoring of ON/OFF operation due to the built-in
operation indicator mechanism.
• Same outline dimensions as the standard models of G2A.
Ordering Information
Contact form
DPDT
Classification
Standard model
Arc barrier equipped model
Fully sealed model
Plug-in terminals
G2AK-232A
G2AK-232AY
G2AK-234A
PCB terminals
G2AK-2321P
---
---
Note: 1. When placing your order, add the coil voltage rating to the model number as shown below.
Example: G2AK-232A 100 VAC
Rated coil voltage
2. The applicable rated voltage range can be increased by connecting an external resistor. Refer to Specifications for details.
3. Models meeting UL standards must be specified when ordering. Add "-US" after the model number.
Model Number Legend
G2AK-@@@@@-@
1 23 4 5 6
1. Number of Poles (Contact Form)
2: DPDT
2. Contact Type
3: Crossbar bifurcated
3. Enclosure Construction
2: Casing
4: Fully sealed
4. Terminal Shape
A: Plug-in terminal
1P: PCB terminal
5. Safety Breaking Mechanism
None: No
Y: Arc barrier
6. Approved Standards
None: Standard
US: UL-approved
Arc barrier equipped model
Fully sealed model
The arc barrier equipped model is a relay designed to prevent arc short- The fully sealed model is a relay in a gas-tight plastic enclosure and thus
circuiting between phases and can be used in a circuit which has poten- exhibits stable performance in an adverse atmosphere of harmful gas,
tial difference between phases. The switching power of such a circuit moisture, or powdery dust.
with potential difference must be limited to less than
1/2 the rated load when using this Relay.
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
1