ES2-THB Datasheet, PDF (1/4 Pages) Omron Electronics LLC – in a Compact Body. Controller Set Provides Superior Humidity Control and Temperature/ Humidity Control.
Humidity Sensor Temperature/Humidity Sensor
ES2-HB ES2-THB
Detect Humidity within an Accuracy of ±3%
in a Compact Body. Controller Set Provides
Superior Humidity Control and Temperature/
Humidity Control.
• Employs high-polymer-resistive Sensor with superior durability.
• Compact and lightweight.
• Measurement ranges of 20% to 95% for humidity and 0 to 55qC
for temperature.
Ordering Information
Name
Humidity Sensor
ES2-HB
Temperature/Humidity Sensor
ES2-THB
Humidity Sensor Module (See note.) ES2-M
Model
Note: This is a replacement item. One Module is provided with the
ES2-HB/-THB. Always attach the Humidity Sensor Module
when using the ES2-HB/-THB. Approximately 7 VDC will be
output for the humidity output if the Module is not attached or is
incompletely attached.
Specifications
Humidity Sensor
section
High-polymer resistive
Humidity detection 20 to 95%
range
Humidity detection r3% (25qC, 40 to 80%)
accuracy
Power supply voltage 24 VDC (See note 1.)
Operating voltage
range
85% to 110% of power supply voltage
Current consumption 10 mA max.
Humidity output
1 to 5 V (for humidity of 0% to 100%)
Permissible load impedance: 100 k: min.
(Use a 1:1 connection when connecting to
an E5@K.)
Temperature Sensor Platinum resistance thermometer
Section (See note 2.)
Temperature
detection range
0 to 55qC
Temperature output Pt100: 3 wire (See note 4.)
Communications cable 5 m
length
Operating temperature 0 to 55qC, humidity of 95% max.
and humidity range
(See note 3.)
Storage temperature
and humidity range
(See note 3.)
20 to 60qC, humidity of 95% max.
Degree of protection IP 20 equivalent
Weight
ES2-HB: Approx. 41 g (excluding cables)
ES2-THB: Approx. 43 g (excluding
cables)
Note: 1. The maximum ripple voltage of 2% p-p max.
The recommended power supply is the OMRON S82K.
2. ES2-THB only.
3. Do not use or store the Sensor for an extended period at a
humidity of 90% or more.
4. Pt100 (JIS C 1604-1989) is used for the measuring
elements. Set Pt100 for input sensor type of the
Temperature Controller.
Dimensions
Note: All units are in millimeters unless otherwise indicated.
ES2-HB Humidity Sensor
ES2-THB Temperature/Humidity Sensor
50
22
50
Cover
4 dia.
37
37
4 dia.
ES2-M Humidity Sensor Module
21
12.7
17.5
Note: Firmly insert the connector all the way in when mounting the
ES2-M to the Sensor.
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.