CJ1W-TS562 Datasheet, PDF (1/2 Pages) Omron Electronics LLC – INSTRUCTION SHEET
Model
CJ1W-TS562
RTD input unit
INSTRUCTION SHEET
Thank you for purchasing an OMRON product. Read this
instruction sheet thoroughly and familiarise yourself with the
functions and characteristics of the product before using it.
To ensure safe and correct use of this Unit, also read the
Operation- and Programming Manuals for your CJ1 PLC system.
Keep this instruction sheet for future reference.
OMRON MANUFACTURING OF THE NETHERLANDS B.V.
 OMRON Corporation 2004
All Rights Reserved
■ Unit Description
The CJ1W-TS562 is a 6-channel input unit for Pt100 and Pt1000
RTD’s. It can be installed in any CJ1-series PLC system.
It is classified as a basic I/O unit, occupying 48, 64 or 96 I/O points,
depending on the number of activated inputs.
Always verify that the maximum I/O capacity of the CJ1 CPU is
sufficient for the number of required I/O points.
■ Nomenclature
Unit status indicators
• RUN
(green)
• ERC
(red)
Sensor error indicators
• 1-6
(red)
Removable Terminal Block
• Connections for
RTDs 1 through 6
DIP switches
(remove terminal block for access)
• Select input types (Pt100/Pt1000)
• Select filter functions
• Select number of active inputs (1-6)
Terminal Block latch
• Slide down to remove
• Slide up to lock
■ Wiring
• Use the same length and type of leadwire for each RTD’s
terminals A, B, and B’, so that the leadwire impedances will be
the same. 2-wire connection can be used by shorting B-B’, but
the specified indication accuracy cannot be guaranteed.
• For activated but unused inputs, short-circuit the A–B and B–B’
terminals, to prevent unstable readout on the other inputs.
• Keep the input wiring away from power lines including AC power
supply lines and high-power lines. Do not run the I/O lines in the
same duct or conduit as power lines.
• The input circuits are galvanically isolated from the PLC’s I/O bus,
but there is no galvanic isolation between individual inputs. All B’
terminals are interconnected in the unit.
• Always ground the terminal on the Power Supply Unit of the
PLC. In case of shielded sensor wiring, connect the shields to the
same grounding point as the PLC.
■ General Specifications
Unit classification
Compatible Racks
Max. number of
Units
CPU Unit data area
for inputs
Insulation resistance
Dielectric Strength
Internal current
consumption
Dimensions
Weight
Other
CJ-series Basic I/O Unit
CJ-series CPU Rack or
CJ-series Expansion Rack
10 Units/Rack max.
(This requires a CJ1G or CJ1H CPU)
Basic I/O area CIO0000 – 0999
(3, 4 or 6 words allocated in IO Table)
20 MΩ min. (at 500 V DC) between
input terminals and external AC
terminals (Power Supply Unit)
500 VAC 50/60 Hz for 1 min. (detection
current: 1 mA),
between Input terminals and external
AC terminals (Power Supply Unit)
250 mA max., 5 V DC,
from the CJ1 I/O bus.
31 x 90 x 65 mm (W x H x D)
150 g max.
Other general specifications conform to
the CJ-series general specifications.
See Operation Manual W393.
■ Characteristics
Temperature Sensor
Number of inputs
Measurement range
Indication resolution
Leadwire
compensation
Temperature value
Data representation
Indication accuracy
over full operational
range (0 – 55 °C
ambient temperature)
Input response time
(per active input)
Input update cycle
time (all active inputs)
I/O refresh time
(influence on PLC
cycle time)
Pt100 or Pt1000 (IEC 60751)
1 to 6
Pt100: -200.0 to +650.0 °C
Pt1000: -200.0 to +650.0 °C
0.1 °C
Automatic, measured on B’ terminals,
updates one sensor in each scan cycle.
16-bit signed integer in units of 0.1 °C:
#F830 = -200.0 °C, #1964 = +650.0 °C
± 0.5 % of indicated value or ± 0.8 °C
(whichever is larger) ± 1 digit max.
when using 3-wire connection.
40 ms (100 Hz suppression)
67 ms (60 Hz suppression)
80 ms (50 Hz suppression)
400 ms (50+60 Hz suppression)
[number of active inputs + 1] x [input
response time] + 40 ms
1-3 inputs (48pt mode): 0.008 ms
4 inputs (64pt mode): 0.011 ms
5-6 inputs (96pt mode): 0.016 ms
■ LED indicators
Name
RUN
(Green)
ERC
(Red)
Sensor
Error
1–6
(Red)
State
OFF
ON
OFF
ON
OFF
ON
All ON
Description
Fatal error or no power supply.
• Check the host PLC’s CPU status, and the
status of other I/O units. If all other units
function normally, replace the Unit
Unit functions normally.
No fatal errors.
Incorrect DIP switch setting
Fatal error in the Unit.
• Check the CPU unit for error codes.
• Re-start the PLC system.
• If the ERC LED is still lit, replace the unit.
• Measurement of the corresponding channel is
within range, or
• Channel has been deactivated by DIP switch
settings
• Measured temperature out-of-range, or
• RTD broken wire or short circuit
Calibration data not found or incorrect. The Unit
should be returned to OMRON for calibration.