8PFA1 Datasheet, PDF (1/11 Pages) Omron Electronics LLC – Floatless Level Controller (Ultra High-sensitivity Type) 61F-UHS/-HSL
Floatless Level Controller (Ultra High-sensitivity Type)
61F-UHS/-HSL
Ideal for Detecting Ice, Pure Water, or
Humidity
• Applicable for detecting ice, pure water steam, humidity, or other
substances that conduct electricity poorly.
• Two types of model available: Ultra high-sensitivity and variable
ultra high-sensitivity.
Refer to Safety Precautions for Floatless Level
Controllers.
■ Ordering Information
Type
Ultra high-sensitivity
Model
Ultra high- 61F-UHS
sensitivity 61F-UHS
Variable ultra high-
sensitivity
Model
61F-HSL
61F-HSL
■ Ultra High-sensitivity Models
Use these models for sensing objects such as ice, high-purity distilled water, moisture, or other objects with low electrical conductivity.
Specifications
Item
Supply voltage
Operating voltage range
Interelectrode voltage
Interelectrode current
Power consumption
Interelectrode operate resistance
Interelectrode release resistance
Cable length
Control output
Ambient temperature
Ambient humidity
Insulation resistance
Dielectric strength
Life expectancy
Weight
High-sensitivity 61F-UHS
100, 200, or 220 VAC; 50/60 Hz
85% to 110% of rated voltage
24 VAC
Approx. 1 mA AC max.
3.2 VA max.
0 to approx. 1 M: (see note 1)
Approx. 5 M to f :
5 m (see note 2)
0.3 A, 220 VAC (Inductive load: cosI = 0.4)
1 A, 220 VAC (Resistive load)
Operating:–10qC to 55qC
Operating:45% to 85% RH
100 M: max. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min
Electrical: 50,000 operations min.
Mechanical: 5,000,000 operations min.
Approx. 210 g
Variable high-sensitivity 61F-HSL
24, 100, 110, 200, or 220 VAC; 50/60 Hz
13 VDC max.
Approx. 1 mA DC max.
0 to approx. 5 M: (variable)
Operate resistance + 2.5 M: max.
(see note 3)
2 A, 220 VAC (Inductive load: cosI = 0.4)
5 A, 220 VAC (Resistive load)
Electrical: 500,000 operations min.
Mechanical: 5,000,000 operations min.
Note: 1. Use 61F-UHS for detecting water leakage with high specific resistance. Connect a sensor cable between terminals 1 and 7.
2. Two Electrodes can be connected to the 61F-HSL. Use them for an alarm, not for creating a self-holding circuit.
3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become shorter as
the cable diameter or number of conductors becomes larger. For more details, refer to Safety Precautions for Floatless Level Controllers.
4. It is recommended that the cable length be kept as short as possible since the Electrode circuit current is at DC micro-current level. More-
over, the Electrodes will corrode rapidly if the current is allowed to constantly flow between the Electrodes.
Be careful with the electrode polarity and grounding when wiring.
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.