English
Language : 

PXIE-8108 Datasheet, PDF (5/7 Pages) National Instruments Corporation – Intel Core 2 Duo T9400 processor(2.53 GHz dual core)
2.53 GHz Dual-Core Embedded Controller for PXI Express
Specifications
Specifications subject to change without notice.
Features
Processor...............................................
Chipset...................................................
Front-side bus........................................
System memory (RAM)..........................
PXI Express 4-link configuration............
Ethernet.................................................
Hard drive
Base...................................................
Extended temperature and
24/7 operation option...................
Video......................................................
Serial......................................................
Parallel...................................................
GPIB ......................................................
Hi-Speed USB........................................
ExpressCard/34 .....................................
Intel Core 2 Duo T9400
(2.53 GHz dual-core)
Mobile Intel GM45 Express Chipset
1066 MHz
1 GB dual-channel DDR2 RAM PC2
6400 (standard); 4 GB dual-channel
DDR2 RAM PC2 6400 (maximum)
4 x1 links
10/100/1000BASE-TX, RJ45 connector
80 GB minimum, 5400 rpm, internal
2.5 in., 9.5 mm Serial ATA 1.0 interface
80 GB minimum, 5400 rpm, internal
2.5 in., 9.5 mm Serial ATA 1.0 interface
Integrated Graphics (Mobile Intel
GM45 Express Chipset)
1 (RS232)
IEEE 1284 Type C miniature connector
(adapter cable not included)
PCI-GPIB/TNT, micro D25 connector
IEEE 488 and HS488 transfers
4
1 (34 mm slot)
Power Requirements
Voltage (V)
+3.3
+5
+12
-12
+5 VAUX
Typical
2.25
1.25
2.00
0.00
0.33
Current (A)
Maximum
3.00
1.80
2.80
0.00
0.40
Physical
Board dimensions..................................
Slot requirements..................................
Compatibility..........................................
Weight...................................................
4-slot 3U PXI module,
8.1 by 13 by 21.6 cm (3.2 by 5.1 by 8.5 in.)
One system slot plus three controller
expansion slots
Fully compatible with PXI Specification
0.983 kg (2.17 lb) typical
Environment
Maximum altitude.................................
Pollution degree.....................................
Indoor use only.
2,000 m (800 mbar)
(at 25 °C ambient temperature)
2
Operating Environment
Ambient temperature range1
Base ...................................................... 5 to 50 °C2
(tested in accordance with
IEC-60068-2-1 and IEC-60068-2-2)
Extended temperature range................. 0 to 55 °C
(tested in accordance with
IEC-60068-2-1 and IEC-60068-2-2)
Relative humidity range......................... 10 to 90% noncondensing
(tested in accordance with
IEC-60068-2-56)
1For chassis that are not available in the online catalog at ni.com, contact National Instruments for
supported operating temperatures.
25 to 40 °C for the NI PXI-1000B DC.
Storage Environment
Ambient temperature range
Base ......................................................
Extended temperature range.................
Relative humidity range.........................
-40 to 65 °C
(tested in accordance with
IEC-60068-2-1 and IEC-60068-2-2)
-40 to 70 °C
(tested in accordance with
IEC-60068-2-1 and IEC-60068-2-2)
5 to 95% noncondensing
(tested in accordance
with IEC-60068-2-56)
Shock and Vibration
Operating shock.....................................
Random vibration
Operating...........................................
Nonoperating....................................
30 g peak, half-sine, 11 ms pulse
(tested in accordance with
IEC-60068-2-27; test profile developed
in accordance with MIL-PRF-28800F)
5 to 500 Hz, 0.3 grms
(with solid-state hard drive)
5 to 500 Hz, 2.4 grms
(tested in accordance with
IEC-60068-2-64; nonoperating test
profile exceeds the requirements of
MIL-PRF-28800F, Class 3)
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)
5