English
Language : 

FP-AI-100 Datasheet, PDF (3/4 Pages) National Instruments Corporation – Analog Input Modules for Compact FieldPoint and FieldPoint
Analog Input Modules for
Compact FieldPoint and FieldPoint
Specifications (contintued)
Module
[c]FP-AI-100
Input Range
Voltage
[c]FP-AI-102
Current
Voltage
[c]FP-AI-110
Voltage
Current
Input Range
With
Nominal
Overranging
0 to 1 V
0 to 1.2 V
0 to 5 V
0 to 6 V
0 to 15 V
0 to 18 V
0 to 30 V
0 to 36 V
±1 V
±1.2 V
±5 V
±6 V
±15 V
±18 V
±30 V
±36 V
0 to 20 mA
0 to 24 mA
4 to 20 mA
3.5 to 24 mA
±20 mA
±24 mA
0 to 20 V
–
0 to 60 V
–
0 to 120 V
–
±20 V
–
±60 V
–
±120 V
–
0 to 1 V
0 to 1.04 V
0 to 5 V
0 to 5.2 V
0 to 10 V
0 to 10.4 V
±60 mV
±65 mV
±300 mV
±325 mV
±1 V
±1.04 V
±5 V
±5.2 V
±10 V
±10.4 V
0 to 20 mA
0 to 21 mA
4 to 20 mA
3.5 to 21 mA
±20 mA
±21 mA
Isolation Voltage
Maximum isolation voltage ............................. 250 Vrms, Installation Category II
Channel-to-channel isolation ........................... No isolation between channels
Transient overvoltage....................................... 2,300 Vrms
Physical Characteristics
LED indicators
POWER (green) .......................................... Power on and self-test passed
READY (green) ........................................... Module configured and ready
Dimensions (including terminal base).............. 10.9 by 10.9 by 9.1 cm (4.3 by 4.3 by 3.6 in.)
Weight
[c]FP-AI-110, [c]FP-AI-111 .......................... 136 g (4.8 oz)
[c]FP-AI-100, [c]FP-AI-102 .......................... 145 g (5.1 oz)
Power Requirement
Power from network module
[c]FP-AI-110, [c]FP-AI-111 .......................... 350 mW
[c]FP-AI-100, [c]FP-AI-102 .......................... 400 mW
Environment
Operating temperature..................................... -40 to 70 °C
Storage temperature ........................................ -55 to 85 °C
Relative Humidity ............................................. 10 to 90%, noncondensing
Shock and Vibration
These specifications apply only to Compact FieldPoint. NI recommends Compact FieldPoint if your
application is subject to shock and vibration.
Operating vibration, random
(IEC 60068-2-64) ........................................ 10 to 500 Hz, 5 grms
Operating vibration, sinusoidal
(IEC 60068-2-6) .......................................... 10 to 500 Hz, 5 g
Operating shock
(IEC 60068-2-27) ........................................ 50 g, 3 ms half sine, 18 shocks at 6 orientations;
30 g, 11 ms half sine, 18 shocks at 6 orientations
EEfffeeccttiivvee
RReessoolluuttiioonn
1.5 mV
5 mV
15 mV
25 mV
1.5 mV
5 mV
25 mV
40 mV
15 µA
15 µA
20 µA
15 mV
40 mV
70 mV
25 mV
70 mV
125 mV
25 µV
90 µV
190 µV
3 µV
16 µV
40 µV
190 µV
380 µV
500 nA
500 nA
700 nA
Offset Error
Typical
Maximum
15 to 35 °C
–40 to 70 °C
1.5 mV
15 mV
6 mV
27 mV
15 mV
45 mV
30 mV
70 mV
2 mV
20 mV
10 mV
40 mV
30 mV
90 mV
60 mV
160 mV
20 µA
45 µA
20 µA
45 µA
40 µA
110 µA
20 mV
100 mV
50 mV
150 mV
100 mV
250 mV
40 mV
175 mV
120 mV
220 mV
350 mV
700 mV
50 µV
650 µV
180 µV
1500 µV
300 µV
2500 µV
30 µV
500 µV
40 µV
600 µV
75 µV
850 µV
300 µV
2500 µV
650 µV
4000 µV
1 µA
10 µA
1 µA
10 µA
1 µA
10 µA
Gain Error
Typical
Maximum
15 to 35 °C
–40 to 70 °C
0.09%
0.50%
0.09%
0.50%
0.12%
0.55%
0.22%
0.55%
0.08%
0.50%
0.08%
0.55%
0.11%
0.60%
0.20%
0.55%
0.09%
0.51%
0.09%
0.51%
0.06%
0.55%
0.1%
0.3%
0.1%
0.3%
0.1%
0.3%
0.1%
0.3%
0.1%
0.3%
0.1%
0.3%
0.03%
0.1%
0.03%
0.1%
0.03%
0.1%
0.03%
0.1%
0.03%
0.1%
0.03%
0.1%
0.03%
0.1%
0.03%
0.1%
0.04%
0.2%
0.04%
0.2%
0.04%
0.2%
Safety
This product is designed to meet the requirements of the following standards of safety for electrical
equipment for measurement, control, and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 3121-1, UL 61010C-1
• CAN/CSA C22.2 No. 1010.1
For UL, hazardous location, and other safety certifications, refer to the product label or to ni.com
Electromagnetic Compatibility
CE, C-Tick, and FCC Part 15 (Class A) Compliant
Emissions.......................................................... EN 55011 Class A at 10 m FCC Part 15A above 1 GHz
Immunity........................................................... EN 61326:1997 + A2:2001, Table 1
For EMC compliance, operate this device with shielded cabling.
CE Compliance
This product meets the essential requirements of applicable European Directives, as amended for
CE Marking, as follows:
Low-Voltage Directive (safety)......................... 73/23/EEC
Electromagnetic Compatibility
Directive (EMC).......................................... 89/336/EEC
Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory compliance
information. To obtain the DoC for this product, visit ni.com/hardref.nsf/ and search by model number
or product line.
Module
[c]FP-AI-100, [c]FP-AI-102
[c]FP-AI-110
[c]FP-AI-111
Filter Settings
–
50 Hz
60 Hz
500 Hz
50 Hz
60 Hz
500 Hz
Update Rate
(All Channels)
2.8 ms
1.470 s
1.230 s
0.173 s
1.230 s
1.050 s
0.290 s
Input Bandwidth
(–3 dB)
170 Hz
13 Hz
16 Hz
130 Hz
13 Hz
16 Hz
130 Hz
National Instruments • Tel: (800) 433-3488 • Fax: (512) 683-9300 • info@ni.com • ni.com 3