Typical for -40 to 70 °C unless otherwise noted.
Input and Output Characteristics
Number of input channels..................... 4
Number of output channels................... 4
ADC resolution....................................... 12 bits
Type of ADC........................................... Successive approximation
DAC resolution....................................... 12 bits
Type of DAC........................................... R-2R
Update rate (all channels)..................... 1.7 kHz (588 μs)
Voltage Inputs
Effective resolution................................
Input impedance....................................
Input signal bandwidth..........................
11.3 bits
1.5 MW
350 Hz
cFP-AIO-600 Gain Errors
Voltage Input Range
Gain Errors at 15 to 35 °C
0-5 V
0.03% typ, 0.04% max
0-10 V
0.03% typ, 0.04% max
0-15 V
0.03% typ, 0.04% max
0-30 V
0.03% typ, 0.04% max
±5 V
0.03% typ, 0.04% max
±10 V
0.03% typ, 0.04% max
±15 V
0.03% typ, 0.04% max
±30 V
0.03% typ, 0.04% max
Gain Errors at -40 to 70 °C
0.11% typ, 0.16% max
0.11% typ, 0.16% max
0.11% typ, 0.16% max
0.11% typ, 0.16% max
0.13% typ, 0.19% max
0.13% typ, 0.19% max
0.13% typ, 0.19% max
0.13% typ, 0.19% max
cFP-AIO-600 Offset Errors
Voltage Input Range
Offset Errors at 15 to 35 °C
0-5 V
4 mV typ, 9 mV max
0-10 V
6 mV typ, 14 mV max
0-15 V
8 mV typ, 18 mV max
0-30 V
13 mV typ, 32 mV max
±5 V
6 mV typ, 14 mV max
±10 V
10 mV typ, 23 mV max
±15 V
14 mV typ, 32 mV max
±30 V
25 mV typ, 59 mV max
Offset Errors at -40 to 70 °C
6 mV typ, 15 mV max
8 mV typ, 20 mV max
10 mV typ, 24 mV max
15 mV typ, 37 mV max
8 mV typ, 20 mV max
12 mV typ, 29 mV max
16 mV typ, 38 mV max
28 mV typ, 64 mV max
Current Inputs
Effective resolution................................
Input impedance....................................
Overcurrent protection...........................
Overvoltage protection..........................
Input signal bandwidth..........................
Gain errors
15 to 35 ºC.........................................
-40 to 70 ºC........................................
11.3 bits
105 W
±100 mA
±10 V
400 Hz
0.08% typ, 0.18% max
0.25% typ, 0.66% max
cFP-AIO-600 Offset Errors
Voltage Input Range
Offset Errors at 15 to 35 °C
0-20 mA
9 μA typ, 20 μA max
4-20 mA
9 μA typ, 20 μA max
±20 mA
16 μA typ, 38 μA max
Offset Errors at -40 to 70 °C
9 μA typ, 20 μA max
9 μA typ, 20 μA max
17 μA typ, 38 μA max
Current Outputs ([c]FP-AIO-600)
Output ranges........................................ 0-20 or 4-20 mA, programmable
(0-21 or 3.5-21 mA with overranging)
Output type............................................ Current source
(external power supply required)
External power supply........................... 10-30 VDC, 125 mA
for four output channels
Internal voltage drop............................. 3 V
Resistive load........................................ Up to 1 kW with 24 VDC power supply
Protection............................................... Short-circuit and open-circuit
Default power-up state......................... 0 mA Isolation Voltage
Current Output Range
(with Overrange)
0 to 21 mA
3.5 to 21 mA
Accuracy at 15 to 35 °C
(% of Output Value;
% of Full Scale)
±0.03%; ±0.13%
±0.03%; ±0.16%
Accuracy at -40 to 70 °C
(% of Output Value;
% of Full Scale)
±0.14%; ±0.2%
±0.14%; ±0.23%
Isolation Voltage
Maximum isolation voltage...................
Channel-to-channel isolation................
Transient overvoltage............................
250 Vrms, Installation Category II
No isolation between channels
2,300 Vrms
Dynamic Characteristics
Maximum update rate........................... 1,700 updates/s
Slew rate............................................... 0.4 mA/μs
Physical Characteristics
LED indicators
POWER (green)..................................
READY (green)...................................
Fault status (red)...............................
Dimensions
(FP only, including terminal base).....
Weight
FP-AIO-600........................................
cFP-AIO-600.......................................
Power on and self-test passed
Module configured and ready
Open circuit
10.7 by 10.9 by 9.1 cm
(4.2 by 4.3 by 3.6 in.)
141 g (4.9 oz)
111 g (3.9 oz)
Power Requirement
Power from network module................. 350 mW
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)