Specifications subject to change without notice. The following
specifications are typical for the range -40 to 70 °C unless
otherwise noted.
Memory
cFP-2200..............................................
cFP-2210..............................................
cFP-2220..............................................
Memory lifetime (nonvolatile) ............
128 MB nonvolatile;
128 MB DRAM
128 MB nonvolatile;
256 MB DRAM
256 MB nonvolatile;
256 MB DRAM
100,000 writes per block
Network
Network interface...............................
Compatibility .......................................
Communication rates..........................
Maximum cabling distance.................
10BASE-T and
100BASE-TX Ethernet
IEEE 802.3
10 Mb/s, 100 Mb/s, autonegotiated
100 m/segment
Serial Ports
cFP-2200.............................................. 1 RS232 port
cFP-2210.............................................. 2 RS232 ports
cFP-2220.............................................. 3 RS232 ports; 1 RS485 port
RS232 (DTE) Ports
Baud rate.............................................
Data bits..............................................
Stop bits..............................................
Parity ...................................................
Flow control ........................................
Up to 115,200 b/s
5, 6, 7, 8
1, 1.5, 2
Odd, Even, Mark, Space
RTS/CTS, XON/XOFF, DTR/DSR
RS485 (DTE) Port
Baud rate.............................................
Data bits..............................................
Stop bits..............................................
Parity ...................................................
Flow control ........................................
Wire mode ..........................................
Continuous ......................................
Dielectric withstand .......................
USB Port (cFP-2220 only)
Maximum data rate ...........................
Maximum current ...............................
9,600 to 115,200 b/s
5, 6, 7, 8
1, 1.5, 2
Odd, Even, Mark, Space
XON/XOFF
4-wire isolation voltage,
port to earth ground
100 Vrms
740 Vrms, verified by 5 s test
12 Mb/s
500 mA
Power Requirements
Caution: You must use a National Electric Code (NEC) UL-listed
Class 2 power supply with cFP-22xx controllers.
Power supply range ............................ 11 to 30 VDC
Recommended power supply
cFP-BP-4 system ............................. 15 W
cFP-BP-8 system ............................. 20 W
Power consumption ............................ 6.1 W + 1.1 (I/O module
power requirements)
Physical Characteristics
If you need to clean the controller, wipe it with a dry towel.
Screw-terminal wiring ........................ Use copper conductor wire with
10 mm (0.39 in.) of insulation
stripped from the end
External digital I/O terminals ......... 16 to 28 AWG
Power supply terminals .................. 14 to 30 AWG
Torque for screw terminals................. 0.5 to 0.6 N•m (4.4 to 5.3 lb•in.)
Weight................................................. 278 g (9.8 oz)
Environmental
The cFP-22xx controllers are intended for indoor use only, but they may
be used outdoors if mounted in a suitably sealed enclosure.
Operating temperature
(IEC 60068-2-1, IEC 60068-2-2)...........
Storage temperature
(IEC 60068-2-1, IEC 60068-2-2)...........
Operating humidity
(IEC 60068-2-56)..................................
Storage humidity (IEC 60068-2-56).....
Maximum altitude...............................
Pollution degree (IEC 60664) ..............
-40 to 70 °C
-55 to 85 °C
10 to 90% RH, noncondensing
5 to 95% RH, noncondensing
2,000 m
2
Shock and Vibration
To meet these specifications, you must panel mount the Compact FieldPoint
system and affix ferrules to the ends of the power terminal wires.
Operating shock (IEC 60068-2-27) ......
Operating vibration, random
(IEC 60068-2-64)..................................
Operating vibration, sinusoidal
(IEC 60068-2-6)....................................
30 g, 11 ms half sine; 50 g,
3 ms half sine; 18 shocks at
6 orientations
5 grms, 10 to 500 Hz
5 g, 10 to 500 Hz
Safety Voltages
Connect only voltages that are within these limits
V terminal to C terminal ..................... 35 V max, Measurement Category I
Caution: Do not connect the system to signals or use for measurements
within Measurement Category II, III, or IV.
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)