English
Language : 

CFP-RLY-421 Datasheet, PDF (2/3 Pages) National Instruments Corporation – Relay Modules for Compact FieldPoint
Relay Modules for Compact FieldPoint
V
C
To next channel
cFP-RLY-421
V
C
VSUP
NO Sourcing
Load
IC
COM
+
or
–
AC
NO
Load
+
IC
–
IC
NC
VSUP
COM
Load
cFP-RLY-423
Figure 1. Wiring Schematics for RLY Modules
Ordering Information
NI cFP-RLY-421 ..........................................................777318-421
NI cFP-RLY-423 ..........................................................777318-423
Recommended Compact FieldPoint System Products
NI cFP-2020 ..............................................................777317-2020
NI cFP-BP-4 ..................................................................778617-04
NI cFP-CB-1 ..................................................................778618-01
NI PS-5 Power Supply ..................................................778805-90
NI Developer Suite Professional Control Edition..........777906-03
BUY ONLINE!
Visit ni.com/info and enter cfprly421, and/or cfprly423.
Specifications
Typical for –40 to 60 °C unless otherwise noted.
Relay Characteristics
Number of channels
cFP-RLY-421 ...............................................
cFP-RLY-423 ...............................................
Relay type
cFP-RLY-421 ...............................................
cFP-RLY-423 ...............................................
Maximum switching capacity (resistive load)
AC ............................................................
DC ............................................................
(cFP-RLY-421) .............................................
(cFP-RLY-423) .............................................
Minimum switching load .................................
Off-state leakage current.................................
DC ............................................................
50/60 Hz ....................................................
On resistance (typical)......................................
Expected relay life
Mechanical ................................................
Electrical (at 30 cpm).................................
Operate time
cFP-RLY-421 ...............................................
cFP-RLY-423 ...............................................
Release time
cFP-RLY-421 ...............................................
cFP-RLY-423 ...............................................
Bounce time
cFP-RLY-421 ...............................................
cFP-RLY-423 ...............................................
Contact material
cFP-RLY-421 ...............................................
cFP-RLY-423 ...............................................
8
4
SPST, normally open, nonlatching
SPDT, nonlatching
1.5 A at 250 VAC
1.5 A at 0–35 VDC
1.5 A at 40 VDC
1 A at 55 VDC
0.4 A at 120 VDC
10 mA at 5 VDC
(120 VDC/250 VAC)
0.12 µA
8 µA
100 mΩ
2 x 107 operations/s (cFP-RLY-421)
1 x 107 operations/s (cFP-RLY-423)
300,000 operations at 1.5 A, 35 VDC
100,000 operations at 1.5 A, 250 VAC
<10 ms
<10 ms typ, 13 ms max
<10 ms
5 ms typ, 7 ms max
10 ms max
3 ms typ, 6 ms max
Gold-plated silver cadmium oxide
Silver cadmium oxide
Power Requirement (from Network Module)
cFP-RLY-421 ...................................................... 1.95 W
cFP-RLY-423 ...................................................... 1.0 W
Physical Characteristics
LED indicators
Power (green) ............................................ Indicates power is on and self-test passed
Ready (green)............................................. Indicates module is configured and ready
<0...7> or <0...3>........................................ Indicates on/off state of each contact
Dimensions (including terminal base).............. 10.9 by 10.9 by 9.1 cm (4.3 by 4.3 by 3.6 in.)
Weight
cFP-RLY-421 ............................................... 136 g (4.8 oz)
cFP-RLY-423 ............................................... 156 g (5.5 oz)
Isolation Voltage
Maximum isolation voltage .............................
Channel-to-channel isolation ...........................
Transient overvoltage.......................................
250 Vrms, Installation Category II
No isolation between channels
2,300 Vrms
Environmental
FieldPoint modules are intended for indoor use only. For outdoor use, they must be mounted inside
a sealed enclosure.
Operating temperature..................................... -40 to 60 °C
Storage temperature ........................................ -55 to 85 °C
Relative humidity ............................................. 10 to 90%, noncondensing
Maximum altitude ............................................ 2,000 m; at higher altitudes the isolation voltage ratings
must be lowered.
Pollution Degree............................................... 2
Safety
This product is designed to meet the requirements of the following standards of safety for electrical
equipment for measurement, control, and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 3121-1, UL 61010C-1
• CAN/CSA C22.2 No. 1010.1
For UL, hazardous location, and other safety certifications, refer to the product label or to ni.com
Electromagnetic Compatibility
CE, C-Tick, and FCC Part 15 (Class A) Compliant
Emissions.......................................................... EN 55011 Class A at 10 m
FCC Part 15A above 1 GHz
Immunity........................................................... EN 61326:1997 +A2:2001, Table 1
For EMC compliance, you must operate this device with shielded cabling.
CE Compliance
This product meets the essential requirements of applicable European Directives, as amended for
CE Marking, as follows:
Low-Voltage Directive (safety)......................... 73/23/EEC
Electromagnetic Compatibility
Directive (EMC).......................................... 89/336/EEC
Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory compliance
information. To obtain the DoC for this product, visit ni.com/hardref.nsf/ and search by model number
or product line.
2 National Instruments • Tel: (800) 433-3488 • Fax: (512) 683-9300 • info@ni.com • ni.com