English
Language : 

CFP-AI-118 Datasheet, PDF (2/4 Pages) National Instruments Corporation – Analog Input Module for Compact FieldPoint
Analog Input Module for Compact FieldPoint
Specifications
Typical for -40 to 70 °C temperature range and for operation with
the 10 Hz filter enabled unless otherwise noted.
Input Characteristics
Number of channels............................
Maximum signal input range..............
Maximum voltage
(V+ or V- to earth) ...............................
ADC resolution....................................
Type of ADC ........................................
8 differential
±15 V (±15.75 V with overranging)
250 Vrms, Measurement
Category II
16 bits (refer to table)
Delta-sigma
Effective Resolution by Input Range and Filter Setting
Nominal Input
Range (V)
With Overranging (V)
±1
±1.05
±5
±5.25
±10
±10.5
±15
±15.75
0 to 1
0 to 1.05
0 to 5
0 to 5.25
0 to 10
0 to 10.5
0 to 15
0 to 15.75
1Includes quantization errors and typical RMS noise.
Effective Resolution1
(No Filtering) (µV)
100
160
320
480
100
100
160
240
Effective Resolution1 with
10 Hz Filter (µV)
32
160
320
480
16
80
160
240
All-channel sample rate
With 10 Hz filter .............................
Without filtering .............................
Input bandwidth (-3 dB) ......................
3.45 kHz1
10.42 kHz1
3 kHz minimum
Common-mode rejection at 60 Hz, with 50 Ω source impedance and no
filtering
Channel to channel.........................
Channel to ground ..........................
Crosstalk attenuation..........................
RMS noise...........................................
Peak-to-peak noise .............................
Settling time to 1 LSB
Full-scale step (-15 to 15 V) ...........
1% step...........................................
Semaphore acquisition jitter ..............
Monotonicity .......................................
Input resistance ..................................
Input capacitance................................
Overvoltage protection .......................
110 db
110 db
>100 dB
100 µV
700 µV
2.1 ms
1.6 ms
None
Warranted over the operating
temperature range
1 MΩ
<50 pF
±250 V
1The all-channel update rate refers to the time the module takes to sample all channels.
The overall system update rate is affected by other factors, such as the aggregate
module update rate and software loop rate. To calculate the system update rate, visit
ni.com/info and enter “systemrate.”
Accuracy by Input Range and Temperature Range
Nominal Input
Range (V)
±1
±5
±10
±15
0 to 1
0 to 5
0 to 10
0 to 15
Typical Accuracy at 15 to 35 °C
(% of Reading; % of Full Scale)
±0.037; ±0.006
±0.037; ±0.003
±0.037; ±0.003
±0.037; ±0.003
±0.037; ±0.006
±0.037; ±0.003
±0.037; ±0.003
±0.037; ±0.003
Warranted Accuracy at 15 to 35 °C
(% of Reading; % of Full Scale)
±0.086; ±0.036
±0.066; ±0.009
±0.064; ±0.005
±0.063; ±0.004
±0.111; ±0.036
±0.071; ±0.009
±0.066; ±0.005
±0.065; ±0.004
Gain error drift .................................... 7.4 ppm/°C
Offset error drift.................................. 3 µV/°C
Isolation Voltage
Isolation voltage is verified by a dielectric withstand test.
Channel-to-channel isolation
Continuous...................................... 100 Vrms
Withstand ....................................... 750 Vrms, 5 s max
Channel-to-backplane isolation
Continuous...................................... 250 Vrms
Withstand ....................................... 2,300 Vrms, 5 s max
Channel-to-ground isolation
Continuous...................................... 250 Vrms
Withstand ....................................... 2,300 Vrms, 5 s max
Physical Characteristics
LED indicators
Power (green)
Ready (green)
Dimensions..........................................
Weight.................................................
Warm-up time .....................................
127.1 by 73.3 by 23.9 mm
(5.00 by 2.89 by 0.94 in.)
117 g (4.1 oz)
30 minutes
Power Requirements
Power from network module .............. 1.125 W
Environment
Operating temperature .......................
Storage temperature...........................
Relative humidity ................................
Maximum altitude...............................
Pollution degree..................................
-40 to 70 °C
-40 to 85 °C
10 to 90%, noncondensing
2,000 m; at higher altitudes the
isolation voltage ratings must
be lowered
2
Shock and Vibration
Operating vibration, random
(IEC 60068-2-64) .............................
Operating vibration, sinusoidal
(IEC 60068-2-6) ...............................
Operating shock
(IEC 60068-2-27) .............................
10 to 500 Hz, 5 grms
10 to 500 Hz, 5 g
50 g, 3 ms half sine, 18 shocks
at 6 orientations; 30 g, 11 ms
half sine, 18 shocks at
6 orientations
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)