D1U54P-W-1200-12-HxxPC Series
54mm 1U Front End AC-DC Power Supply Converter
WIRING DIAGRAM FOR OUTPUT
Dotted lines show optional remote sense connections.
Optional remote sense lines can be attached to a load that is a distance
away from the power supply to improve regulation at the load.
V1_SENSE (Main Output Remote Sense)
V1_SENSE (Main Output Remote Sense)
E3
+12V main output
6-10
D1U54P
12V load
1-5 +12V main output return
D3
B5 (or D4)
V1_SENSE_R
ISHARE
+12V main output 6-10 E3
D1U54P
+12V main output return 1-5
V1_SENSE_R D3
ISHARE B5 (or D4)
A1,B1,C1,D1,E1
B4
A2,B2
VSB
PS_ON
VSB_return
VSB load
FET, BJT, wire
or switch (debounced )
to turn on +12V main output
VSB A1,B1,C1,D1,E1
PS_ON B4
VSB_return A2,B2
A5 (or A3) PS_KILL
PS_KILL A5 (or A3)
CURRENT SHARING NOTES
Main Output: Current sharing is achieved using the active current share method. (See wiring diagram for connection details.)
Current sharing can be achieved with or without remote sense connected to the common load.
+VSB outputs can be tied together for redundancy but total combined output power must not exceed the rated standby power. The +VSB output has internal ORing MOSFET for
additional redundancy / internal short protection.
The current share pin B5 (or D4 for alternate pin out model) is a connection between the units. It is input and/or output as the voltage on the line controls the current share. A power
supply will respond to a change in this voltage but a power supply can also change the voltage depending on the load drawn from it. On a single unit this would read 8V at 100%
load. For two units sharing load then this should read 4V for perfect current sharing.
Up to 8 units can be paralleled together. Please consult your Murata sales representative if operation with more than 8 units in parallel is needed.
www.murata-ps.com/support
D1U54P-W-1200-12-HxxPC.A09 Page 7 of 8