STATUS INDICATOR AND CONTROL SIGNALS
Status
Input OK LED
Output OK LED
Fault LED
See also ACAN36 for additional LED operation details.
FAN MONITORING
Status
Fan monitoring is available through the I2C interface
EMISSIONS AND IMMUNITY
Characteristic
Conducted Emissions
Radiated Emissions
ESD Immunity
Radiated Field Immunity
Electrical Fast Transients/Burst Immunity
Surge Immunity
RF Conducted Immunity
Magnetic Field Immunity
Ring Wave
D1U4CS-D-2100-5x-HA3DC
DC-DC Front End Power Supply
Conditions
Green
Blinking at 1Hz
Off
Green
Blinking at 1Hz
Red
Off
Description
DC input present and within range
DC input present and outside range
DC input not present
Outputs are present and within regulation
Power limit or overcurrent condition
Fault condition present
No fault condition detected
Conditions
Both fans running normally
One fan failed (or rotor locked)
Both fans failed (or rotors locked)
Description
PMBus CMD E5 Byte 2 bit 3
PMBus CMD E5 Byte 2 bit 3
PMBus CMD E5 Byte 2 bit 3
Standard
FCC 47 CFR Part 15/CISPR 22/EN55022
FCC 47 CFR Part 15/CISPR 22/EN55022
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-4-12
Compliance
Class A, 6dB margin
Class A, 6dB margin
8kV contact discharge
15kV operational air discharge
10 V/m, Performance Criteria A
2kV, Performance Criteria A
1kV/1kV, Performance Criteria A
10Vrms, 80% AM, 1kHz, Performance Criteria A
30 A/m
1kV, Performance Criteria A