English
Language : 

D1U3CS-W-1300F-12-HA4EC Datasheet, PDF (1/5 Pages) Murata Manufacturing Co., Ltd. – 81mm Front End AC-DC Power Converter
www.murata-ps.com
D1U3CS-W-1300F-12-Hx4EC Series
81mm Front End AC-DC Power Converter
PRODUCT OVERVIEW
The D1U3CS-W-1300F-12-Hx4EC are high efficiency 1300W power factor corrected front end supplies with a 12V main
output and a 5V or 3.3V (20W) standby. Active current sharing is provided to allow up to eight (8) supplies to be operated
in parallel. The supplies may be hot plugged and include integral isolation devices.
The power modules are fully protected from overload and overvoltage and are able to auto-recover from overtemperature
faults. Status LEDS are provided on the front panel and additional control and status reporting is provided by hardware
logic signals and via a PMBus™ digital interface.
A low profile sub 1U height enclosure provides a power density of >23W/in3 that is ideal for delivering reliable, efficient
power to servers, workstations, storage systems and other 12V distributed power systems.
FEATURES
Extended Power Range to 1300W
1.57" (1U) x 11.0" x 3.2"
92% efficiency at 50% FL
12VDC Main output
3.3VSB or 5VSB output (20W)
>23W/in3 power density
N+1 Redundancy Capable; hot plug/swap (up to
8 modules in parallel)
Active current sharing on 12V main output;
integral MOSFET ORING
Over-Voltage, Over-Current; Over-Temperature
Protection
Internal variable speed cooling fans
PMBus™ Power Management Bus
RoHS Compliant
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
Available now at
www.murata-ps.com/en/3d/acdc.html
ORDERING GUIDE
Model Number
D1U3CS-W-1300F-12-HA4EC
D1U3CS-W-1300F-12-HC4EC
Power Output
AC Line & Temp AC Line & Temp
(108-264V; 40°C) (90-264V; 50°C)
1300W
1200W
Main
Output
12V
Standby
Output
5V
3.3V
Airflow
Back to Front
INPUT CHARACTERISTICS
Parameter
Voltage Operating Range
Input Frequency
Turn-on Input Voltage
Turn-off Input Voltage
Maximum Current @ VIN = 200Vac
Maximum Current @ VIN = 90Vac
Inrush Current
Power Factor
Efficiency (230Vac) excluding fan load
Conditions
Ramp Up
Ramp Down
1300W @ 40°C (max)
1200W @ 50°C (max)
Cold start between 0 to 200ms
At 230Vac; FL
20% FL
50% FL
100% FL
Min Typ Max
90 115/230 264
47 50/60 63
81
85
89
70.5 74.3 78.0
8
15
25
0.99
88
92
92
Units
Vac
Hz
Vac
Arms
Apk
%
OUTPUT VOLTAGE CHARATERISTICS
Output
Voltage
Parameter
Conditions
Min Typ Max Units
Voltage Set Point Accuracy
Line & Load Regulation
12
Vdc
11.4
12.6
Ripple & Noise1
20MHz Bandwidth
150 mV P-P
12V
Output Current (230Vac)
0
108.3 A
Output Current (120Vac)
108.3
Output Current (90Vac)
100
Load Capacitance
30,000 μF
Voltage Set Point
Line & Load Regulation
3.3
Vdc
3.2
3.4
3.3VSB Ripple Voltage & Noise1
20MHz Bandwidth
100 mV P-P
Output Current
0
6
A
Load Capacitance
10,000 μF
Voltage Set Point
Line & Load Regulation
5.0
Vdc
4.85
5.1
5VSB Ripple Voltage & Noise1
20MHz Bandwidth
50 mV P-P
Output Current
0
4
A
Load Capacitance
10,000 μF
1 Ripple and noise are measurements are to be performed with a parallel combination of a 0.1μF ceramic capacitor and 10μF tantalum
capacitance on each of the power module output measurement nodes. A short coaxial cable shall be used.
Ḥ
For full details go to
www.murata-ps.com/rohs
CB
Test Certificate
and Test Report
www.murata-ps.com/support
D1U3CS-W-1300F-12-Hx4EC.A01 Page 1 of 5