CONNECTOR TO CUSTOMER SYSTEM
Signal Connector: MOLEX # 39-28-5204 OR TYCO # 281282-1
Mating Connector: MOLEX # 0039521204
Pin Assignment
Signal Name
Description
1
AC_OK11
Input AC Voltage âOKâ signal output for the 2nd shelf
2
P_Good12
Power good signal output for the 2nd shelf
3
PS_On13
Power enable for the 2nd shelf
4
NOT USED
5
AC_OK01
Input AC Voltage âOKâ signal output for the local shelf
6
P_Good02
Power good signal output for the local shelf
7
PS_OnO3
Power enable for the local shelf
8
NOT USED
9
I2C Adr2
Address input 2
10
I2C Clock4
I2C serial clock bus
11
I2C Data4
I2C serial data bus
12
I_SHARE
13
SENSE +5
14
SENSE -5
15
Vsb
Standby voltage output
16
Vsb
Standby voltage output
17
Vsb
Standby voltage output
18
GND
GROUND
19
GND
GROUND
20
GND
GROUND
High Level
Low Level
open drain
< 0.7V
open drain
< 0.7V
> 2.1V (open, or Vsb)
< 0.7V (active, PS:On)
open drain
< 0.7V
open drain
< 0.7V
> 2.1V (open, or Vsb)
< 0.7V (active, PS:On)
> 2.1V, < Vsb
< 0.8V
Vsb
Vsb
I Max
- 2 mA
+ 4 mA
- 2 mA
+ 4 mA
- 1 mA
- 4 mA
- 2 mA
+ 4 mA
- 2 mA
+ 4 mA
- 1 mA
- 4 mA
± 1 mA
All control signals are with respect to Ground. Negative currents exit the power supply.
1 Signal goes low when any one of the three power supplies loses AC
2 Signal goes low when any one of the three power supplies fail
3 In a standalone shelf (without I2C control) Pull this pin to GND to turn on three power supplies at the same time. With I2C control, leave this signal ï¬oat and Use I2C to turn on one power supply at a time.
4 Recomended 10KOhm pull up resistor to host 3.3 or 5V rail
5 Short Sense+ to +Vout and Sens- to GND at the point of load
SHELF TO SHELF CONNECTION
Signal Connector: MOLEX # 39-28-5164 OR TYCO # 281281-1
Pin Assignment
Signal Name
Description
1
AC_OK11
Input AC Voltage âOKâ signal output for the 2nd shelf
2
P_Good12
Power good signal output for the 2nd shelf
3
PS_On13
Power enable for the 2nd shelf
High Level
Low Level
open drain
< 0.7V
open drain
< 0.7V
> 2.1V (open, or Vsb)
< 0.7V (active, PS:On)
I Max
- 2 mA
+ 4 mA
- 2 mA
+ 4 mA
- 1 mA
- 4 mA
4
NOT USED
5
NOT USED
6
I2C Clock4
I2C serial clock bus
Vsb
7
I2C Data4
I2C serial data bus
Vsb
8
I_SHARE
9
SENSE +5
10
SENSE -5
11
Vsb
Standby voltage output
12
Vsb
Standby voltage output
13
Vsb
Standby voltage output
14
GND
GROUND
15
GND
GROUND
16
GND
GROUND