English
Language : 

MVAD065 Datasheet, PDF (2/5 Pages) Murata Power Solutions Inc. – 65W High Density AC/DC Power Supply
ENVIRONMENTAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Operating Altitude
MTBF
Shock
Vibration
Safety (pending)
Warranty
Outside Dimensions
Weight
PROTECTION CHARACTERISTICS
Parameter
Overvoltage Protection
Overcurrent Protection
ISOLATION CHARACTERISTICS
Parameter
Isolation
Leakage Current
Touch Current
EMISSIONS AND IMMUNITY
Characteristic
Input Current Harmonics
Voltage Fluctuation and Flicker
Conducted Emissions
ESD Immunity
Radiated Field Immunity
Electrical Fast Transient Immunity
Surge Immunity
RF Conducted Immunity
Magnetic Field Immunity
Voltage dips, interruptions
www.murata-ps.com/support
MVAD065 Series
PRELIMINARY 65W High Density AC/DC Power Supply
Conditions
Min.
Typ.
Max.
-40
85
Full load
-10
50
50% load
-10
70
Start up
-20
Non-condensing
10
95
Without derating
-200
5000
Telcordia SR-332 M1C3 25°C
1M
Operating, IEC60068-2-27, half-sine 5G,
6ms, 3 times per face, 6 faces
Complies
Non-operating, IEC60068-2-27, half-sine,
30G, 18ms, 3 times per face, 6 faces
Complies
Operating, IEC60068-2-6, 1.0G, 10-150Hz,
10 minutes per axis, on all 3 axes
Complies
Non-operating, IEC60068-2-6, 2.0G,
10-150Hz, 10 minutes per axis, on all 3
axes
Complies
IEC60950-1:2006/A11:2009
UL60950-1 2nd Ed. 2007-03-27, CSA22.2 N0.60950-1 2nd Ed. 2007.03,
EN60950-1:2006+A11:2009
IEC60601-1 Ed. 3 MOOP
ANSI/AAMI ES60601-1 (2005+C1:09+A2:10), CSA 22.2 No. 60601-1 (2008) 3rd Edition MOOP
EN60601-1:2006 3rd ed. MOOP (Evaluated)
CE Marking per LVD
2 years
2.0" x 4.0" x 1.3" (50.8mm x 101.6mm x 33.02mm)
0.27lbs (123g) typical
Units
°C
%
m
Hours
Conditions
Latching (60% load)
Hiccup mode
Min.
Typ.
Max.
Units
110
160
%V1
110
160
%Amax
Conditions
Primary to Chassis
Primary to Secondary
Secondary to Chassis
264Vac, 60Hz, 25°C
264Vac, 60Hz, 25°C
Min.
Typ.
Max.
Units
1500 (1MOOP)
3000 (2MOOP)
Vac
500
Vdc
250
μA
100
μA
Standard
IEC/EN 61000-3-2
IEC/EN 61000-3-3
EN 55022
FCC Part 15
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-4-11
Compliance
Class A
Complies
Class B
Class B
Level 4, Criterion A
Level 2, Criterion A
Level 3, Criterion A
Level 4, Criterion A
Level 2, Criterion A
Level 2, Criterion A
Level 3, Criterion B
MVAD065.A01.D10 Page 2 of 5