English
Language : 

MVAD040-12 Datasheet, PDF (2/5 Pages) Murata Power Solutions Inc. – 40W 2" x 4" AC-DC Power Supply Converter
ENVIRONMENTAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Operating Altitude
MTBF
Shock
Vibration
Safety
Warranty
Outside Dimensions
Weight
PROTECTION CHARACTERISTICS
Parameter
Overvoltage Protection
Overcurrent Protection
ISOLATION CHARACTERISTICS
Parameter
Isolation
Leakage Current
Touch Current
EMISSIONS AND IMMUNITY
Characteristic
Input Current Harmonics
Voltage Fluctuation and Flicker
Conducted Emissions
ESD Immunity
Radiated Field Immunity
Electrical Fast Transient Immunity
Surge Immunity
RF Conducted Immunity
Magnetic Field Immunity
Voltage dips, interruptions
www.murata-ps.com/support
MVAD040 Series
40W 2" x 4" AC-DC Power Supply Converter
Conditions
Min.
Typ.
Max.
-40
85
Full load
50% load
Start up
-20
50
-20
70
-20
Non-condensing
Without derating
10
95
-200
5000
Telcordia SR-332 M1C3 25°C
1M
Operating, IEC60068-2-27, half-sine 5G,
6ms, 3 times per face, 6 faces
Complies
Non-operating, IEC60068-2-27, half-sine,
30G, 18ms, 3 times per face, 6 faces
Complies
Operating, IEC60068-2-6, 1.0G, 10-150Hz,
10minutes per axis, on all 3 axes
Complies
Non-operating, IEC60068-2-6, 2.0G,
10-150Hz, 10minutes per axis, on all 3
axes
Complies
IEC60950-1:2006/A11:2009
UL60950-1 2nd Ed. 2007-03-27, CSA22.2 N0.60950-1 2nd Ed. 2007.03,
EN60950-1:2006+A11:2009
IEC60601-1 Ed. 3 MOOP
ANSI/AAMI ES60601-1 (2005+C1:09+A2:10), CSA 22.2 No. 60601-1 (2008) 3rd Edition MOOP
EN60601-1:2006 3rd ed. MOOP (Evaluated)
CE Marking per LVD
2 years
2.0" x 4.0" x 1.3" (50.8mm x 101.6mm x 33.02mm)
0.27lbs (123g) typical
Units
°C
%
m
Hours
Conditions
Latching (60% load)
Hiccup mode
Min.
Typ.
Max.
Units
110
160
%V1
170
240
%Amax
Conditions
Primary to Earth Ground
Primary to Secondary
Secondary to Earth Ground
264Vac, 60Hz, 25°C
264Vac, 60Hz, 25°C
Min.
Typ.
Max.
Units
1500 (1MOOP)
3000 (2MOOP)
Vac
500
Vdc
250
μA
100
μA
Standard
IEC/EN 61000-3-2
IEC/EN 61000-3-3
EN 55022
FCC Part 15
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-4-11
Compliance
Class A
Complies
Class B
Class B
Level 4, Criterion A
Level 2, Criterion A
Level 3, Criterion A
Level 4, Criterion A
Level 2, Criterion A
Level 2, Criterion A
Level 3, Criterion B
MVAD040.A01 Page 2 of 5