English
Language : 

MVAB120-12 Datasheet, PDF (2/7 Pages) Murata Power Solutions Inc. – 120W 2 x 4 AC-DC Power Supply Converter
MVAB120 Series
120W 2" x 4" AC-DC Power Supply Converter
ENVIRONMENTAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Operating Altitude
MTBF
Shock
Conditions
Full load
50% load
Start up
Non-condensing
Without derating
Telcordia SR-332 M1C3 25°C
Operating, IEC60068-2-27, half-sine 5G, 6ms, 3 times per face,
6 faces
Non-operating, IEC60068-2-27, half-sine, 30G, 18ms, 3 times
per face, 6 faces
Min.
-40
-10
-10
-20
10
-200
1M
Complies
Complies
Typ.
Max.
85
50
70
95
3000
Units
°C
%
m
Hours
Vibration
Operating, IEC60068-2-6, 1.0G, 10-150Hz, 10minutes per axis,
on all 3 axes
Complies
Non-operating, IEC60068-2-6, 2.0G, 10-150Hz, 10minutes per
axis, on all 3 axes
Complies
Safety
Warranty
Outside Dimensions
Weight
IEC60950-1:2005 (2nd Edition); Am1:2009
UL60950-1 2nd Edition,2011-12-19, CSA C22.2 No. 60950-1-07, 2nd Edition,2011-12
EN60950-1:2006 + A11:2009 + A1:2010 + A12:2011
IEC60601-1:2005 + CORR.1(2006) + CORR.2(2007)
ANSI/AAMI ES60601-1 (2005+C1:09 + A2:10), CSA-C22.2 No. 60601-1(2008), MOPP
CE Marking per LVD
2 years
2.0" x 4.0" x 1.35" (50.8mm x 101.6mm x 34.3mm); 2.0" x 4.0" x 1.41" (50.8mm x 101.6mm x 35.8mm) for medical version
MVAB120-12/-01
0.34lbs (155g) typical
MVAB120-24/-01, MVAB120-28/-01, MVAB120-48/-01
0.36lbs (162g) typical
PROTECTION CHARACTERISTICS
Parameter
Overvoltage Protection
Overcurrent Protection
Overtemperature Protection
Conditions
Latching
Hiccup mode
Auto recovery
Min.
Typ.
Max.
110
160
105
150
Complies
Units
%V1
%Amax
ISOLATION CHARACTERISTICS
Parameter
Isolation
Leakage Current (under normal conditions)
Conditions
Min.
Typ.
Max.
Units
Primary to Earth Ground (1MOOP)
1500
Vac
Primary to Secondary (2MOOP or 1 MOPP)
3000
Secondary to Earth Ground
500
Vdc
264Vac, 60Hz, 25°C
500
μA
EMISSIONS AND IMMUNITY
Characteristic
Input Current Harmonics
Voltage Fluctuation and Flicker
Conducted Emissions
ESD Immunity
Radiated Field Immunity
Electrical Fast Transient Immunity
Surge Immunity
RF Conducted Immunity
Magnetic Field Immunity
Voltage dips,interruptions
Standard
IEC/EN 61000-3-2
IEC/EN 61000-3-3
EN 55022
FCC Part 15
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-4-11
Compliance
Class A
Complies
Class B, Class A (at class II equipment)
Class B, Class A (at class II equipment)
Level 4, Criterion A
Level 2, Criterion A
Level 3, Criterion A
Level 3, Criterion A
Level 2, Criterion A
Level 1, Criterion A
Level 3, Criterion B
www.murata-ps.com/support
MVAB120.A13 Page 2 of 7