English
Language : 

D1U86G Datasheet, PDF (2/5 Pages) Murata Power Solutions Inc. – 86mm 1U Front End AC-DC Power Supply Converter
D1U86G-W-460-12-HxxDC Series
86mm 1U Front End AC-DC Power Supply Converter
OUTPUT CHARACTERISTICS
Parameter
Output Rise Monotonicity
Startup Time
Transient Response
Conditions
No voltage excursion
AC ramp up
12V, 50% load step, 0.5A/μs di/dt
12VSB, 50% load step, 0.5A/μs di/dt
Min.
Typ.
Max.
Units
1.5
s
300
600
mV
Current sharing accuracy (up to 8 in parallel)
At 100% load
±10
%
Hot Swap Transients
Holdup Time
All outputs remain in regulation
10
5
%
ms
ENVIRONMENTAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Storage Humidity
Altitude (without derating at 40°C)
Shock
Operational Vibration
MTBF
Safety Approvals (pending)
Input Fuse
Weight
Conditions
Min.
Typ.
Max.
Units
-40
70
°C
0
50
Noncondensing
5
5
90
95
%
3000
m
30G non operating
1G, 10 – 500 Hz, 1.6G (non-operational)
Per Telcordia SR-322 M1C1 @ 40°C
635K
hrs
CSA/UL 60950-1-07-2nd Ed.
IEC 60950-1:2005 (2nd Edition) w Am. 1:2009
EN 60950-1:2006 +A11:2009 +A1:2010
CE Marking per LVD DIRECTIVE 2006/95/EC
Power Supply has internal 6.3A/250V slow blow fuse on the AC line input
1.76 lbs (798g)
PROTECTION CHARACTERISTICS
Output
Voltage
Parameter
Overtemperature (intake)
12V
Overvoltage
Overcurrent
12VSB
Overvoltage
Overcurrent
Conditions
Autorestart
Latching
Latching
Autorecovery
Autorecovery
Min.
Typ.
Max.
Units
57
60
63
°C
13.6
15
V
42
49.8
A
13.6
15
V
3.5
5.0
A
ISOLATION CHARACTERISTICS
Parameter
Insulation Safety Rating / Test Voltage
Isolation
Conditions
Min.
Typ.
Max.
Units
Input to Output - Reinforced
3000
Vrms
Input to Chassis - Basic
1500
Vrms
Main and standby outputs connected directly to chassis
EMISSIONS AND IMMUNITY
Characteristic
Input Current Harmonics
Voltage Fluctuation and Flicker
Conducted Emissions
ESD Immunity
Radiated Field Immunity
Electrical Fast Transient Immunity
Surge Immunity
Radiated Field Conducted Immunity
Magnetic Field Immunity
Voltage dips, interruptions
Standard
IEC/EN 61000-3-2
IEC/EN 61000-3-3
FCC 47 CFR Part 15/CISPR 22/EN55022
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-4-11
Compliance
Complies
Complies
Class B, 6dB margin
Level 3 criteria A
Level 3 criteria B
Level 3 criteria A
Level 3 criteria A
Level 3 criteria A
3 A/m criteria B
230Vin, 100% load, Phase 0°, Dip 100% Duration 10ms (A)
230Vin, 50% load, Phase 0°, Dip 100% Duration 20ms (VSB:A, V1:A)
230Vin, 100% load, Phase 0°, Dip 100% Duration > 20ms (VSB, V1:B)
www.murata-ps.com/support
D1U86G-W-460-12-HxxDC.A03 Page 2 of 5