English
Language : 

SP1470 Datasheet, PDF (1/1 Pages) Murata Power Solutions Inc. – Telephony 750 Watts Uninterruptible Power Supply
SP1470
Celab
Telephony 750 Watts Uninterruptible Power Supply
Specification
Input Voltage
230VAC, +15% - 10% Single Phase
Input Frequency
47 to 63Hz
Emissions/Immunity Standards EMC meets requirement of EN50081-1 & EN50082-1
Inrush Current
15A Typical
Output Voltage
54V to 58V (adjustable by potentiometer)
Output Current Range
0-10A at 56V
Output Regulation
■ Integrated battery management system.
■ Designed for street cabinet applications.
Output Noise & Ripple
■ Non latching thermal protection.
Battery Charging Current
■ 10A output with separate 4A charging facility.
Efficiency
■ Output voltage adjustable from 54V to 58V DC.
■ Automatic and remote controlled battery condition testing. Operating Temperature
■ Comprehensive range of management alarms.
Temperature Coefficient
Load +/- 1%, Line +/- 0.2%
In battery mode the output will be equal to the battery
voltage, less 0.5V
100mV peak to peak, up to 20 MHz
4A DC
>85% at full load
-20°C to +65°C
0.02% per °C
Protective Features
If ambient temperature exceeds 65°C the power supply is protected by a non-latching thermal cut-out.
Insulation - Input to Chassis
1500Vrms
Insulation - Output to Chassis
Insulation - Input to Output
3750Vrms
Insulation - Output to Output
Safety Standards
Meets BSEN60950, LVD Compliant, CE marked.
Current Limit
Trip and restart, 20A +/- 1A
100Vrms
100Vrms
Overvoltage Protection
Low Battery Disconnect
Auto Battery Test Feature
Trip and restart, 64V +/- 1V
42.5V +/- 0.5V
The power supply will automatically load check the battery condition approximately every 20 days (or longer if re-
quired) for approximately 20 minutes to establish that the battery is ‘good’.
If the battery voltage is below 47 volts, alarm 4 will operate.
Alarms
The following 6 alarms are isolated and have a pair of contacts that can be factory configured open or closed in normal operation.
Alarm 1: Input Mains Good
Alarm 2: Output Voltage Good
Alarm 3: Power Supply Good
Alarm 4: Battery Good
Alarm 5: Alarms 1 to 4 in Series
Alarm 6: Thermal Cut Out
Alarm Indicators
Alarms 1 to 4 - Four Green LED’s
Output Current Indicator
LED display of total output current (including battery charging current) in 2A increments to 16A.
Mechanical Specification
Mains Input
Size
Weight
Specification Note:
IEC 320 connector with 10A fusing
19” rack x 2U high x 240mm deep
6kg
For any requirements not specified above, please contact the sales department.
■ The SP1470 series has been specifically designed to reliably withstand the very high and low
temperatures experienced in street cabinets.
■ The battery management system enhances the life of the batteries by controlling the charging
current and avoiding deep discharge.
■ Regular battery test loading monitors battery health without risk of system failure.
Murata Power Solutions (Celab) Ltd, 25 Woolmer Way, Bordon, Hampshire, GU35 9QE
www.murata-ps.com/celab
Tel: +44 (0) 1420 477011 Fax: +44 (0)1420 487476