English
Language : 

D2U5T-H3-5000-380-HU3C Datasheet, PDF (1/8 Pages) Murata Power Solutions Inc. – AC-DC Three Phase Power Converter
D2U5T-H3-5000-380-HU3C
AC-DC Three Phase Power Converter
FEATURES
 5KW (480Vac), 3.5KW (230Vac) Output
Power
 Very High Efficiency; 95.4% @ 50% FL
 380V High Voltage Main Output
 3.3V or 5V Standby Output
 Nominal Dim’s: 5.1"(W) x 18"(L) x 3.3" (2U
 16.5 watts/cubic inch power density
 N+1 redundant (including hot docking)
 Droop sharing on Main Output
 Over-voltage, over-current, over-
temperature protections
 Internal cooling fan
 I2C Bus Interface with status indicators
 Optional 19" power shelf
 RoHS compliant
 Two-year warranty
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
Available now at:
www.murata-ps.com/en/3d/acdc.html
For full details go to
www.murata-ps.com/rohs
PRODUCT OVERVIEW
The D2U5T-H3-5000-380-HU3C is a High Efficiency 3500/5000 watt, power factor corrected three phase
power supply for 230/480Vac lines with a 380V high voltage (HVDC) main output and a selectable 5V or
3.3V (20W) standby. The unit is provided with Droop Sharing and up to three (3) power modules may be
operated in parallel.
The power module is hot pluggable. The module is able to protect and recover from over temperature
faults, and has status LEDs on the front panel and additional logic and PMBus status signals.
Their 2U package and >16.5W/cubic inch power density make them ideal for delivering reliable,
efficient power to servers, workstations, storage systems and other 380V HVDC distributed power
systems. An optional power shelf is also available that accommodates up to three (3) power modules.
ORDERING GUIDE
Model Number
D2U5T-H3-5000-380-HU3C
Power
5000W
Main Output
380V
Standby Output
3.3V or 5V
(Selectable)
Airflow
Front to Back
INPUT CHARACTERISTICS
Parameter
Input Frequency
Input Voltage Operating Range
Turn-on Voltage (Ramp-up)
Turn-off Voltage (Ramp-down)
Maximum Input Current
Inrush Current
Power Factor, Range 1, 60Hz
Power Factor, Range 2, 60Hz
Conditions
Range 1
Range 2
Range 1
Range 2
Range 1
Range 2
Cold Start
600W, 230 Vac
1750W (50%), 230 Vac
3500W (100%), 230 Vac
600W, 480 Vac
2500W (50%), 480 Vac
5000W (100%), 480 Vac
Min Typ
Max Units
47 50/60 63 Hz
180
264 Vac
320
528 Vac
170
Vac
280
Vac
150
Vac
260
Vac
13
Arms
30 Apk
0.992
0.998
0.998
0.910
0.995
0.995
OVERALL CHARACTERISTICS
Parameter
Conditions
Min Typ Max Units
Output Power
Range 1
Range 2
3500
5000
W
700W (20%), 230Vac
89.5
Efficiency, Range 1
1750W (50%), 230Vac
93.6
3500W (100%), 230Vac
500W (20%), 230Vac
94.2
92.6
%
Efficiency, Range 2
2500W (50%), 230Vac
95.4
5000W (100%), 230Vac
95.4
The following curves represent the achieved efficiency performance for the D2U5T-H3-5000-380-Hu3C
product compared against a recognized industry standard for efficiency rating.
The D2U5T-H3-5000-380-HU3C offers performance in excess of the industry standard limit as a required
percentage of loading.
Test methodology as per Ecova Generalized Test Protocol for Calculating the Energy Efficiency of Internal
AC-DC and DC-DC Power Supplies Revision 6.7
CB
Test Certificate
and Test Report
www.murata-ps.com/support
D2U5T-H3-5000-380-HU3C.A02 Page 1 of 8