D1U54-D-650-12-HBXC Datasheet, PDF (1/9 Pages) Murata Power Solutions Inc. – 54mm 1U Front End DC-DC Power Supply Converter | |||
|
D1U54-D-650-12-HBxC Series
54mm 1U Front End DC-DC Power Supply Converter
PRODUCT OVERVIEW
The D1U54-D-650-12-HBxC products are very high efï¬ciency DC input 650 watt front end supplies provided with a
12V main and a 12V Standby output. An active (analogue) current share characteristic is provided to allow units to be
operated in parallel. The power supply may be hot plugged; recovers from overtemperature faults, and has status
LEDs on the front panel in addition to hardware signal logic and PMBus⢠status signals. The low proï¬le 1U package
and 21.4W/cubic inch power density make them ideal for delivering reliable, efï¬cient power to networking
equipment, workstations, storage systems and other 12V distributed power architectures.
ORDERING GUIDE
Part Number
Murata Internal Power Output
Part Number -44 to -72Vdc
D1U54-D-650-12-HB3C
D1U54-D-650-12-HB4C
M1879
M1878
650W
Main
Output
12Vdc
Standby
Output
12Vdc
Airï¬ow
Front to Back
Back to front
FEATURES
ï® 650W output power
ï® 93% efï¬ciency at 50% load
ï® 12V main output
ï® 12V standby output
ï® 1U height:
ï® 2.15" x 9.00" x 1.57"
ï® 54.5mm x 228.6mm x 40mm
ï® 21.4 Watts per cubic inch density
ï® N+1 redundancy capable, including hot plugging
ï® Active (analogue) current sharing on 12V main
output; ORING FET
ï® Overvoltage, Overcurrent, Overtemperature
protection
ï® Internal cooling fan (variable speed)
ï® PMBusâ¢/I2C interface with status indicators
ï® RoHS compliant
ï® Two Year Warranty
www.murata-
ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
Available now at: www.murata-ps.com/en/3d/acdc.html
INPUT CHARACTERISTICS
Parameter
Conditions
Input Source Voltage Operating Range
Turn-on Input Voltage
Ramp up
Turn-off Input Voltage
Ramp down
Input current at Vin = -53Vdc
650W
Inrush Current
Cold start (25°C) between 0 to 200ms
Min.
-44
-42.5
-37.5
20% load
90
Efï¬ciency (-53Vdc) excluding fan load 50% load
93
100% load
92
Nom. Max. Units
-53 -72 Vdc
-43 -43.5
-38 -39.5 Vdc
13.6
Adc
25
Apk
%
OUTPUT VOLTAGE CHARACTERISTICS
Nominal
Output
Voltage
Parameter
Conditions
Min.
Typ.
Max. Units
Output Set Point Accuracy 50% load; Tamb =25°C 11.96 12.00 12.04 Vdc
Line and Load Regulation
Setpoint; temperature;
line and load
-1.0%
+1.0
%
%
12V Ripple Voltage & Noise1, 2
20MHz Bandwidth
Output Current Range
0
120 mV p-p
54.2 A
Load Capacitance
500
4000 μF
Output Set Point Accuracy 50% load; Tamb = 25°C 11.96 12.00 12.04
Line and Load Regulation
Setpoint; temperature;
line and load
11.7
12VSB Ripple Voltage & Noise1
20MHz Bandwidth
12.3 Vdc
120 mV p-p
Output Current
0
2
A
1 Ripple and noise is measured with a parallel combination 0.1μF of ceramic and 10μF of tantalum capacitance on each
measurement node.
2 Measurements assume the use of the minimum load capacitance as specified for the main 12V output and a minimum load of 5%.
Below 5% loading the overall voltage deviation shall be within ±2.5%.
For full details go to
www.murata-ps.com/rohs
CB
Test Certificate
and Test Report
www.murata-ps.com/support
D1U54-D-650-12-HBxC.A02 Page 1 of 9
|
▷ |