English
Language : 

D1U3CS-W-1200-12-HXXC Datasheet, PDF (1/6 Pages) Murata Power Solutions Inc. – 81mm 1U Front End AC-DC Power Supply Converter
www.murata-ps.com
To Be Discontinued*
FEATURES
„„1200W output power
„„80 PLUS® Gold efficiency
„„12V main output
„„3.3V or 5V standby output of 20W
„„1U height: 3.20" x 11.00" x 1.57"
„„21.7 Watts per cubic inch density
„„N+1 redundancy capable, including hot
plugging (up to 8 in parallel)
„„Active current sharing on 12V main output;
ORing FET
„„Overvoltage, overcurrent, overtemperature
protection
„„Internal cooling fan (variable speed)
„„PMBus™ I²C interface with status indicators
„„RoHS compliant
„„Two-year warranty
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
Available now at
www.murata-ps.com/en/3d/acdc.html
FwowrwFfou.mrllfuudrllaedttaea-tpailsisls.cggooomt/toroohs
www.murata-ps.com/rohs
D1U3CS-W-1200-12-HxxC Series
81mm 1U Front End AC-DC Power Supply Converter
PRODUCT OVERVIEW
The D1U3CS-W-1200-12-HxxC series are 80 PLUS Gold efficiency 1200 watt, power factor corrected front end supplies
with a 12V main output and a 5V or 3.3V (20W) standby. They have active current sharing and up to 8 supplies may be
operated in parallel. The supplies may be hot plugged, they recover from overtemperature faults, and have status LEDs
on their front panel in addition to logic and PMBus™ status signals. Their low profile 1U package and >21W/cubic inch
power density make them ideal for delivering reliable, efficient power to servers, workstations, storage systems and
other 12V distributed power systems.
ORDERING GUIDE
Part Number
D1U3CS-W-1200-12-HC4C
D1U3CS-W-1200-12-HA4C
D1U3CS-W-1200-12-HC3C
D1U3CS-W-1200-12-HA3C
Power Output Power Output
High Line AC Low Line AC
1200W
1200W
1200W
1200W
1000W
1000W
1000W
1000W
Main
Output
12V
12V
12V
12V
Standby
Output
3.3V
5V
3.3V
5V
Airflow
Back to front
Back to front
Front to back
Front to back
INPUT CHARACTERISTICS
Parameter
Conditions
Min. Nom. Max. Units
Voltage Operating Range
90 115/230 264 Vac
Frequency
47
50/60
63
Hz
Turn-on Voltage
Turn-off Voltage
Ramp up
Ramp down
81
85
70.5 74.3
89
78
Vac
Maximum Current at Vin=200Vac
Maximum current at Vin=90Vac
1200W
1000W
8
15
Arms
Inrush Current
Cold start between 0 to 200msec
25 Apk
Power Factor
At 230Vac, full load
0.99
20% load
88
Efficiency (230Vac) excluding fan load 50% load
92
%
100% load
92
OUTPUT VOLTAGE CHARACTERISTICS
Output
Voltage
Parameter
Conditions
Min. Typ. Max. Units
12V
3.3VSB
5VSB
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Output Current (230Vac)
Output Current (120Vac)
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Output Current
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Output Current
Load Capacitance
20MHz Bandwidth
20MHz Bandwidth
20MHz Bandwidth
12.0
11.4
12.6
Vdc
120 mV p-p
0
0
98.3
81.7
A
30000
µF
3.3
3.2
3.4
Vdc
100 mV p-p
0
6
A
10000
µF
5.0
4.85
5.15
Vdc
50 mV p-p
0
4
A
10000
µF
1 Ripple and noise are measured with 0.1 uF of ceramic capacitance and 10 uF of tantalum capacitance on each of the
power supply outputs. A short coaxial cable with 50ohm scope termination is used.
CB
Test Certificate
and Test Report
www.murata-ps.com/support
*LAST TIME BUY: 3/31/2017. CLICK HERE FOR DISCONTINUANCE NOTICES.
D1U3CS-W-1200-12-HxxC.B01 Page 1 of 6