English
Language : 

D1U Datasheet, PDF (1/5 Pages) Murata Power Solutions Inc. – AC/DC Front End Power Supply
www.murata-ps.com
FEATURES
RoHS compliant
2800W (220Vac) Output Power
-52V Main output, 12V standby output
1U sized; dimensions 5.5"x11.4"x1.61"
27.7 Watts per cubic inch density
N+1 redundancy capable,
including hot-docking
Active current sharing or droop current
sharing
Over-voltage, over-current,
over-temperature protection
Internal cooling fans
I²C Bus interface with status indicators
Optional 1U x 19" power-shelf
D1U-H-2800-52-HBxC Series
AC/DC Front End Power Supply
PRODUCT OVERVIEW
The D1U-H-2800 is a 2800 Watt, power-factor-corrected (PFC) front-end power supply for hot-swapping
redundant systems. The main output is -52V and standby output of 12V. Packaged in 1U low profile, it is
designed to deliver reliable bulk power to telecom systems or any -52V distributed power architecture
systems requiring high power density. The highly efficient electrical and thermal design with internal
cooling fans supports reliable operation conditions. The D1U-H-2800 is designed to auto-recover from
over-current and over-temperature faults. Status information is provided with front panel LEDs, logic
signals and I2C management interface. Three units can be packaged into an optional 19" 1U power shelf
to provide up to 8.4kW of power.
SELECTION GUIDE
Part Number
D1U-H-2800-52-HB1C
D1U-H-2800-52-HB1DC
Power Output
High Line AC
2800W
2800W
Main Output
-52V
-52V
Standby
Output
12V
12V
Airflow Current Share
Front to back
Front to back
Active
Droop
INPUT CHARACTERISTICS
Parameter
Input Voltage Operating Range
Input Frequency
Turn-on Input Voltage
Turn-off Input Voltage
Maximum Rated Input Current
Inrush Current
Inrush Current
Power Factor
Conditions
Min. Typ. Max. Units
170 230 264 Vac
47
55
63
Hz
Ramp up
Ramp down
160
155
170
165
Vac
200VAC
16 Arms
Cold start
50
Apk
Cold start between 0-1msec
100 Apk
Output load >90%
95%
Output load >50%
75%
OUTPUT VOLTAGE CHARACTERISTICS
Output
Voltage
Parameter
Conditions
Voltage Set Point Accuracy
Line and Load Regulation
-52V Ripple Voltage & Noise
20MHz Bandwidth
Output Current
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
12Vsb Ripple Voltage & Noise
Operating Range
Load Capacitance
Min. Typ. Max. Units
-52
51.48
52.52
Vdc
520 mV p-p
1
54
A
6800
μF
11.2
12
12.4
Vdc
120 mV p-p
0
0.5
A
1000
μF
1 Ripple and noise are measured with 0.1 uF of ceramic capacitance and 10 uF of tantalum capacitance on each of
the power supply outputs. The output noise requirements apply over a 0 Hz to 20 MHz bandwidth. A short coaxial
cable with 50ohm scope termination is used.
Ḥ
For full details go to
www.murata-ps.com/rohs
www.murata-ps.com/support
D1U-H-2800-52-HBxC.A08 Page 1 of 5