English
Language : 

D1U-W-1600-12-HC2C Datasheet, PDF (1/7 Pages) Murata Power Solutions Inc. – AC/DC Front End Power Supply + S1U Power Shelf
D1U-W-1600-12-Hx Series
AC/DC Front End Power Supply + S1U Power Shelf
FEATURES
RoHS compliant
1600W (220Vac), 1200W (110Vac)
Output power
12V Main output,
3.3V or 5V standby output
1U sized; dimensions 12” x 4.75” x 1.6”
17.5 Watts per cubic inch density
N+1 redundancy capable,
including hot-docking
Active current sharing on main output
Over-voltage, over-current,
over-temperature protection
Internal cooling fans
I²C Bus Interface with status indicators
Optional 1U x 19” power-shelf
www.murata-ps.com
PRODUCT OVERVIEW
The D1U-W-1600 is a 1600 Watt, power-factor-corrected (PFC) front-end power supply for hot-swapping redundant
systems. The main output is 12V and standby output of either 5V or 3.3V. Packaged in 1U low profile, it is designed
to deliver reliable bulk power to servers, workstations, storage systems or any 12V distributed power architecture
systems requiring high power density. The highly efficient electrical and thermal design with internal cooling fans
supports reliable operation conditions. The D1U-W-1600 is designed to auto-recover from over-temperature faults.
Status information is provided with front panel LEDs, logic signals and I2C management interface. Three units can be
packaged into an optional 19” 1U power shelf to provide up to 4.8kW of power.
The S1U-X3 is a 1U x 19” EIA Rack Mount Power Shelf designed for holding three D1U Front End Power Supplies
in current sharing applications. It is intended for distributed power architecture applications in the Servers, Storage
Networking and Data Communications markets. There are two lug terminal connections for #2 AWG cabling for the DC
output. System connection through the I2C bus reports the performance status of the power supplies within the power
shelf. Two Power Shelves can operate in parallel by an optional Shelf-to-Shelf cable, doubling the power output to the
maximum capability of 9.6kW for two 12V power shelves.
SELECTION GUIDE
Part Number
D1U-W-1600-12-HC2C
D1U-W-1600-12-HA2C
D1U-W-1600-12-HC1C
D1U-W-1600-12-HA1C
Part Number
S1U-3X-16-A-12-RC
Power Output Power Output
High Line AC Low Line AC
1600W
1200W
1600W
1200W
1600W
1200W
1600W
1200W
Description
Power shelf for 12V D1U
Main Output
12V
12V
12V
12V
Standby
Output
3.3V
5V
3.3V
5V
Airflow
Back to front
Back to front
Front to back
Front to back
INPUT CHARACTERISTICS
Parameter
Input Voltage Operating Range
Input Frequency
Turn-on Input Voltage
Turn-off Input Voltage
Maximum Input Current
Inrush Current
Power Factor
Conditions
Min. Typ. Max. Units
Low Line AC
High Line AC
90
180
140
264
Vac
47 50/60 63
Hz
Ramp up
Ramp down
78.5
70.5
86.5
78
Vac
Low Line AC 90Vac
High Line AC 180Vac
15
10
Arms
Cold start between 0-1msec
100 Apk
Output load >90%
95%
Output load >50%
75%
OUTPUT VOLTAGE CHARACTERISTICS
Output
Voltage
Parameter
Conditions
12V
3.3Vsb
5Vsb
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Output Current
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Operating Range
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Operating Range
Load Capacitance
20MHz Bandwidth
20MHz Bandwidth
20MHz Bandwidth
Min.
11.75
0
3.2
0
4.85
0
Typ.
12.12
3.3
5
Max.
12.48
120
131.6
40000
3.4
33
6
1530
5.15
50
4
1530
Units
Vdc
mV p-p
A
μF
Vdc
mV p-p
A
μF
Vdc
mV p-p
A
μF
1 Ripple and noise are measured with 0.1 uF of ceramic capacitance and 2 x 270 uF of OSCON capacitance on each
of the power supply outputs. The output noise requirements apply over a 0 Hz to 20 MHz bandwidth. A short coaxial
cable with 50ohm scope termination is used. See Ripple Test Setup diagram.
Technical enquiries email: toronto@murata-ps.com, tel: +1 (866) 740 1232
CPS_D1U-W-1600-12-Hx.C06 Page 1 of 7