English
Language : 

CPS_D1U-2000-48-HX Datasheet, PDF (1/5 Pages) Murata Power Solutions Inc. – AC/DC Front End Power Supply
www.murata-ps.com
D1U-W-2000-48-Hx Series
AC/DC Front End Power Supply
PRODUCT OVERVIEW
The D1U-W-2000 is a 2000 Watt, power-factor-corrected (PFC) front-end power supply for hot-swapping redun-
dant systems. The main output is 48V and standby output of either 12V, 5V or 3.3V. Packaged in 1U low profile, it is
designed to deliver reliable bulk power to servers, workstations, storage systems or any 48V distributed power archi-
tecture systems requiring high power density. The highly efficient electrical and thermal design with internal cooling
fans supports reliable operation conditions. The D1U-W-2000 is designed to auto-recover from over-temperature
faults. Status information is provided with front panel LEDs, logic signals and I2C management interface. Three units
can be packaged into a 19" 1U power shelf to provide up to 6.0kW of power.
FEATURES
RoHS compliant
2000W (220Vac), 1200W (110Vac)
Output power
48V Main output,
3.3V, 5V or 12V standby output
1U sized; dimensions 4.75"x12.00"x1.61"
21.9 Watts per cubic inch density
N+1 redundancy capable, including hot-docking
Active current sharing on main output
Over-voltage, over-current,
over-temperature protection
Internal cooling fans
I²C Bus Interface with status indicators
Ḥ
For full details go to
www.murata-ps.com/rohs
www.murata-ps.com/support
SELECTION GUIDE
Part Number
D1U-W-2000-48-HC2C
D1U-W-2000-48-HA2C
D1U-W-2000-48-HB2C
D1U-W-2000-48-HB4C
Power Output
High Line AC
2000W
2000W
2000W
2000W
Power Output
Low Line AC
1200W
1200W
1200W
Main Output
48V
48V
48V
Standby
Output
3.3V
5V
12V
1200W
48V
12V
Airflow
Back to front
Back to front
Back to front
Back to front;
variable speed fan
INPUT CHARACTERISTICS
Parameter
Input Voltage Operating Range
Input Frequency
Turn-on Input Voltage
Turn-off Input Voltage
Maximum Input Current
Inrush Current
Power Factor
Conditions
Min. Typ. Max. Units
90 115/230 264 Vac
47 50/60 63
Hz
Ramp up
Ramp down
78.5
70.5
86.5
78
Vac
Low Line AC 90Vac
High Line AC 180Vac
15
10
Arms
Cold start between 0-1msec
90
Apk
Output load >90%
95%
Output load >50%
75%
OUTPUT VOLTAGE CHARACTERISTICS
Output
Voltage
Parameter
Conditions
48V
3.3Vsb
5Vsb
12Vsb
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Output Current
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Operating Range
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Operating Range
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Operating Range
Load Capacitance
20MHz Bandwidth
20MHz Bandwidth
20MHz Bandwidth
20MHz Bandwidth
Min. Typ. Max. Units
46.54
48
49.44 Vdc
480 mV p-p
2
41.3
A
10000 μF
3.2
3.3
3.4
Vdc
50 mV p-p
0
4.5
A
1530 μF
4.85
5
5.15
Vdc
50 mV p-p
0
4
A
1530 μF
11.6
12
12.4
Vdc
120 mV p-p
0
1.7
A
1530 μF
CPS_D1U-W-2000-48-Hx.D01 Page 1 of 5