C1U-W-1200-48-TA1C Datasheet, PDF (1/4 Pages) Murata Power Solutions Inc. – AC/DC Front End Power Supply | |||
|
ht p:/ www.murata-ps.com
FEATURES
ï®ï RoHS compliant
ï®ï 1200W (110/220Vac) Output power
ï®ï 48V Main output,
3.3V, 5V or 12V standby output
ï®ï Dimensions: 1.67â x 5.5â x 14.2â
ï®ï 9.2 Watts per cubic inch density
ï®ï N+1 redundancy capable,
ï®ï Active current sharing on main output
ï®ï Over-voltage, over-current,
over-temperature protection
ï®ï Internal cooling fans
Ḥ
For full details go to
www.murata-ps.com/rohs
www.murata-ps.com
C1U-W-1200-48-Tx Series
AC/DC Front End Power Supply
PRODUCT OVERVIEW
The C1U-W-1200 is a 1200 Watt universal AC input, power-factor-corrected (PFC) front-end power
supply for general applications. The main output is 48V and standby output of either 5V, 3.3V, or 12V.
Packaged in U low proï¬le, it is designed to deliver reliable bulk power to servers, workstations, storage
systems or any 48V distributed power architecture systems requiring high power density. The highly
efï¬cient electrical and thermal design with internal cooling fans supports reliable operation conditions.
The C1U-W-1200 is designed to auto-recover from over-temperature faults.
SELECTION GUIDE
Part Number
C1U-W-1200-48-TA1C
C1U-W-1200-48-TC1C
C1U-W-1200-48-TA2C
C1U-W-1200-48-TC2C
C1U-W-1200-48-TB1C
C1U-W-1200-48-TB2C
Power Output
Universal Line
1200W
1200W
1200W
1200W
1200W
1200W
Main Output
48V
48V
48V
48V
48V
48V
Standby
Output
5V
3.3V
5V
3.3V
12V
12V
Airï¬ow
Front to back
Front to back
Back to front
Back to front
Front to back
Back to front
INPUT CHARACTERISTICS
Parameter
Input Voltage Operating Range
Input Frequency
Turn-on Input Voltage
Turn-off Input Voltage
Maximum Input Current
Inrush Current
Power Factor
Conditions
Ramp up
Ramp down
Output load >90%
Output load >50%
Min. Typ. Max. Units
90
264 Vac
47
55
63
Hz
78.5
70.5
86.5
78
Vac
15 Arms
90
Apk
95%
75%
OUTPUT VOLTAGE CHARACTERISTICS
Output
Voltage
Parameter
Conditions
48V
3.3Vsb
5Vsb
12Vsb
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Output Current
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Operating Range
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Operating Range
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise1
Operating Range
Load Capacitance
20MHz Bandwidth
Min. Typ. Max. Units
46.54
48
49.44
Vdc
480 mV p-p
2
24.6
A
10000 μF
3.3
3.2
3.4
Vdc
50 mV p-p
0
4.5
A
1530
μF
4.85
5
5.15
Vdc
50 mV p-p
0
4
A
1530
μF
11.2
12
12.4
Vdc
120 mV p-p
0
1.7
A
1530
μF
1 Ripple and noise are measured with 0.1 uF of ceramic capacitance and 10 uF of tantalum capacitance on each of
the power supply outputs. The output noise requirements apply over a 0 Hz to 20 MHz bandwidth. A short coaxial
cable with 50ohm scope termination is used.
Technical enquiries email: toronto@murata-ps.com, tel: +1 (866) 740 1232
C1U-W-1200-48-Tx.A04 Page 1 of 4
|
▷ |