DS1750D5S Datasheet, PDF (6/6 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET
6 / // / DS01750D5S / 50 Hz / 380V - 11kV
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based an standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
System
Dimensions (L x W x H)
Open Power Unit (OPU) 4419 x 1836 x 2330 mm
Weight (dry/less tank)
10477 kg
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.
SOUND DATA
// Consult your local MTU Onsite Energy distributor for sound data.
EMISSIONS DATA
// Consult your local MTU Onsite Energy distributor for emissions data.
RATING DEFINITIONS AND CONDITIONS
// Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for
the duration of a power outage. No overload capability for this rating. Ratings are in accordance with ISO 8528-1, ISO-3046-1,
BS 5514, AS 2789, and DIN 6271. Average Load Factor: < 85%. Operating hours/year: max. 500.
// Deration factor:
Altitude: Consult your local MTU Onsite Energy Power Generation distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power Generation distributor for temperature derations.
Rated power is available up to 40°C and 400m above sea level.
Materials and specifications subject to change without notice.