WEIGHTS AND DIMENSIONS
4 / //  / MTU 4R0113 DS50 (45kWe) - Prime
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website
for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
1,781 x 800 x 1,321 mm (70.13 x 31.5 x 52 in)
Weight (dry/less tank)
872 kg (1,920 lb)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
SOUND DATA
Unit Type
Level 0: Open Power Unit dB(A)
Prime Full Load
80.2
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
RATING DEFINITIONS AND CONDITIONS
NOx + NMHC
CO
PM
3.8
0.69
0.22
All units are in g/hp-hr and shown at 100% load
(not comparable to EPA weighted cycle values).
Emission levels of the engine may vary with ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation, etc.
The data was obtained in compliance with US EPA regulations.
The weighted cycle value (not shown) from each engine
is guaranteed to be within the US EPA Standards. 5-mode
emission data per 40 CFR 89 or 40 CFR 1039 (as applicable) is
available upon request.
//  Prime power ratings apply to installations where utility power
is unavailable or unreliable. At varying load, the number of
generator set operating hours is unlimited. A 10% overload
capacity is available for one hour in twelve. Ratings are in
accordance with ISO 8528-1, overload power in accordance
with ISO 3046-1, BS 5514, and AS 2789. Average load
factor: ≤ 75%.
//  Deration Factor:
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
C/F = Consult Factory/MTU Onsite Energy Distributor
N/A = Not Available
MTU Onsite Energy