English
Language : 

MTU10V0068GS75 Datasheet, PDF (4/4 Pages) MTU Onsite Energy Corporation – GAS GENERATOR SET
WEIGHTS AND DIMENSIONS
4 / //  / MTU 10V0068 GS75 (75 kWe) - Standby
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
2,199 x 1,158 x 1,438 mm (86.6 x 45.6 x 56.6 in)
Weight (dry)
1,125 kg (2,481 lb)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
SOUND DATA
Unit Type
Level 0: Open Power Unit dB(A)
Standby Full Load (NG)
75.5
Standby Full Load (LP)
76.1
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
RATING DEFINITIONS AND CONDITIONS
Fuel Type
Natural Gas
Liquid Propane
THC + NOx
7.53
7.65
CO
30.49
47.95
All units are in g/hp-hr and are EPA weighted cycle values.
Emission levels of the engine may vary with ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation, etc.
The data was obtained in compliance with US EPA regulations.
//  Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload
capability for this rating. Ratings are in accordance with
ISO 3046-1, BS 5514, and AS 2789. Average load
factor: ≤ 85%.
//  Deration Factor:
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
C/F = Consult Factory/MTU Onsite Energy Distributor
N/A = Not Available
MTU Onsite Energy
A Rolls-Royce Power Systems Brand