WEIGHTS AND DIMENSIONS
4 / //  / GS75-6S
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
System
OPU
Dimensions (L x W x H)
2,199 x 1,158 x 1,438 mm (86.6 x 45.6 x 56.6 in)
Weight (dry)
1,125 kg (2,481 lb)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
SOUND DATA
Unit Type
Level 0: Open Power Unit dB(A)
Standby Full Load (NG)
75.5
Standby Full Load (LP)
76.1
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
Fuel Type
THC + NOx
CO
Natural Gas
7.5
30.5
Liquid Propane 7.6
48.0
All units are in g/hp-hr.
Engine meets EPA 40 CFR Part 60/90 specifications.
RATING DEFINITIONS AND CONDITIONS
//  Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload
capability for this rating. Ratings are in accordance with
ISO 3046-1, BS 5514, AS 2789, and DIN 6271.
//  Deration Factor:
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
Materials and specifications subject to change without notice.
C/F = Consult Factory/MTU Onsite Energy Distributor
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com