English
Language : 

MTU6R1600DS275 Datasheet, PDF (3/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET
3 / //  / MTU 6R1600 DS275 (275 kWe) - Standby
APPLICATION DATA
//  Engine
//  Fuel Consumption
Manufacturer
Model
Type
Arrangement
Displacement: L (Cu In)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Max. Power: kWm (bhp)
Speed Regulation
Air Cleaner
//  Liquid Capacity (Lubrication)
MTU
6R1600G70S
4-Cycle
6-Inline
10.5 (641)
12.2 (4.8)
15 (5.91)
17.5:1
1,800
ECU 8
312 (418)
±0.25%
Dry
At 100% of Power Rating: L/hr (gal/hr)
At 75% of Power Rating: L/hr (gal/hr)
At 50% of Power Rating: L/hr (gal/hr)
//  Cooling - Radiator System
Ambient Capacity of Radiator: °C (°F)
Max. Restriction of Cooling Air: Intake
and Discharge Side of Rad.: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM)
Heat Rejection to After Cooler: kW (BTUM)
Heat Radiated to Ambient: kW (BTUM)
Fan Power: kW (hp)
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
//  Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
46 (12.2)
45 (11.9)
82 (21.7)
24
950
//  Air Requirements
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Cooled Unit: *m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Generator Set Heat for a
Max. of 25 °F Rise: *m3/min (SCFM)
//  Fuel System
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
Fuel Supply Connection Size
Fuel Return Connection Size
Max. Fuel Lift: m (ft)
Recommended Fuel
Total Fuel Flow: L/hr (gal/hr)
-10 JIC 37° Female
M20 x 1.5 Male Adapter Provided
-6 JIC 37° Female
M14 x 1.5 Male Adapter Provided
5 (16)
Diesel #2
198 (60.4)
//  Exhaust System
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
Temp: m3/min (CFM)
Max. Allowable
Back Pressure: kPa (in. H20)
74 (19.7)
60 (15.9)
46 (12.2)
50 (122)
0.2 (0.8)
277 (73.1)
143 (8,132)
84 (4,777)
34.1 (1,939)
17.8 (23.9)
30 (1,059.4)
396 (13,985)
123.8 (4,374)
430 (806)
72 (2,542.7)
15 (60.2)