3 / //  / MTU 16V2000 DS1100 / 3E / 50 Hz / 380V - 415V
Application data➀
//  Cooling/Radiator System
Coolant flow rate (HT circuit):
m3/h
Heat rejection to coolant:
kW
Heat rejection to charge air:
kW
Heat radiated to ambient:
kW
Fan power for mech. radiator (40°C):
kWm
Fan power for mech. radiator (50°C):
kWm
Air flow required for mech. radiator (40°C) cooled unit:
m3/min
Air flow required for mech. radiator (50°C) cooled unit:
m3/min
Engine coolant capacity (without cooling equipment):
l
Radiator coolant capacity (40°C):
l
Radiator coolant capacity (50°C):
l
Max. coolant temperature (warning):
°C
Max. coolant temperature (shutdown):
°C
Fuel consumption optimized Emission optimized➁
41.6
41.6
370
350
145
205
40
40
43.4
43.4
43.4
43.4
1462
1462
1462
1462
70
70
83
83
104
104
102
102
105
105
//  Exhaust System
Exhaust gas temp. (after turbocharger):
°C 530
515
Exhaust gas volume:
m3/s
2.78
3.07
Maximum allowable back pressure:
mbar 50
50
Minimum allowable back pressure:
mbar 30
30
//  Generator
Protection class IP2x
IP2x
Insulation class H H
Voltage regulation (steady state) ± 0.25%
± 0.25%
Rado interference class N
N
➀ All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
➁ Emission optimized data refer to TA-Luft optimized and NEA (ORDE) optimized/Tier 2 compliant engines.