DS1100D5S Datasheet, PDF (3/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET AIR CHARGE-AIR COOLING | |||
|
◁ |
3 / // / 50 Hz 1100 kVA
STANDARD FEATURESâ
// The engine-generator set complies to G3
// Engine generator set tested according to ISO 8528-5 for
transient response
// Accepts rated load in one step as per NFPA 110
// All engine-generator sets are type and factory tested
// MTU Onsite Energy is a single source supplier
// Global product support
// Cooling System (integral set-mounted; engine driven fan)
// 16V2000 diesel engine (31,84 Liter (1943 cu inch)
displacement; 4-stroke)
// Engine-generator resiliently mounted
// Complete range of accessories
// Brushless, rotating ï¬eld generator (PMG excitation;
250% short circuit capability; 2/3 pitch stator windings)
// Complete system metering
// LCD display
APPLICATION DATA
// Engine
Manufacturer
Model
Type
Arrangement
Displacement: L (cu inch)
Bore: mm (inch)
Stroke: mm (inch)
Compression ratio
Rated speed rpm
Engine Governor
Max power: kWm (bhp)
Speed regulation
Air ï¬lter
// Lube Oil Capacity
MTU
16V2000G65TD
4-Stroke
16-V
1.99 (121)
130 (5.1)
150 (5.9)
16:1
1500
Electronic isochronous
975 (1307)
±0.25%
Dry
// Fuel Consumptionâ
At 100% of power rating:
At 75% of power rating:
At 50% of power rating:
gal/hr
62
45
31
// Cooling/Radiator System
Ambient capacity of radiator: °C
Max. restriction of cooling air, intake,
and discharge side of rad.: kPa (in. H 0)
2
Water pump capacity: l/min (gpm)
Heat rejection to coolant: kW (BTUM)
Heat rejection to after cooler: kW (BTUM)
Heat radiated to ambient: kW (BTUM)
Engine coolant capacity: l (gal)
Coolant to cooler temperature: °C (°F)
Total oil system: l (gal)
102 (27) // Air Requirementsâ
// Electrical
Electric Volts DC
Cold cranking amps under -17.8 °C (0 °F)
24
1000
// Fuel System
Fuel supply connection size
Fuel return connection size
Maximum fuel lift: m (ft)
Recommended fuel
Total fuel ï¬ow: l/hr (gal/hr)
M22x1,5 - 60°/Male
M12x1,5 - 60°/Male
5 (16)
see MTU ï¬uids & lubrication spec.
600 (159)
Aspirating: m3/min (SCFM)
Air ï¬ow required for rad.
cooled unit: m3/min
// Exhaust System
Gas temp. (stack): °C (°F)
Gas volume ï¬ow
temp: m3/min (SCFM)
Maximum allowable
back pressure: kPA
l/hr
g/kwh
234
199
172
195
116
198
40 (optional 50)â
0,2 (0,803)
667 (176)
420 (23,885)
200 (11,374)
45 (2559)
110 (29)
95 (203)
72 (2540)
1236 (43606)
535 (995)
198 (6985)
8,5 (34)
â Represents standard product only.Consult Factory/MTU Onsite Energy distributor for additional conï¬gurations.
â Values in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
â System ratings at 50°C may differ.
â Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
|
▷ |