English
Language : 

DS1050D5S Datasheet, PDF (3/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET WATER CHARGE-AIR COOLING
3 / // / 50 Hz 1050 kVA
STANDARD FEATURES➀
// The engine-generator set complies to G3
// Engine generator set tested according to ISO 8528-5 for
transient response
// Accepts rated load in one step as per NFPA 110
// All engine-generator sets are type and factory tested
// MTU Onsite Energy is a single source supplier
// Global product support
// 16V2000 diesel engine (31,84 Liter (1943 cu inch)
displacement; 4-stroke)
// Engine-generator resiliently mounted
// Complete range of accessories
// Brushless, rotating field generator (PMG excitation;
250% short circuit capability; 2/3 pitch stator windings)
// Complete system metering
// LCD display
APPLICATION DATA
// Engine
Manufacturer
Model
Type
Arrangement
Displacement/cylinder: l (cu inch)
Bore: mm (inch)
Stroke: mm (inch)
Compression ratio
Rated speed rpm
Engine governor
Max power: kWm (bhp)
Speed regulation
Air filter
MTU
16V2000G25TB
4-Stroke
16-V
1.99 (121)
130 (5.1)
150 (5.9)
16:1
1500
Electronic isochronous
890 (1194)
±0.25%
Dry
// Fuel Consumption➁
At 100% of power rating:
At 75% of power rating:
At 50% of power rating:
gal/hr
56
42
28
// Cooling/Radiator System
Water pump capacity: l/min (gpm)
Heat rejection to coolant: kW (BTUM)
Heat rejection to after cooler: kW (BTUM)
Heat radiated to ambient: kW (BTUM)
Engine coolant capacity: l (gal)
// Air Requirements➂
// Lube Oil Capacity
Aspirating: m3/min (SCFM)
Total oil system: l (gal)
102 (27) // Exhaust System
// Electrical
Electric Volts DC
Cold cranking amps under -17.8 °C (0 °F)
// Fuel System
24
1000
Gas temp. (stack): °C (°F)
Gas volume flow
temp: m3/min (SCFM)
Maximum allowable
back pressure: kPA
Fuel supply connection size
Fuel return connection size
Maximum fuel lift: m (ft)
Recommended fuel
Total Fuel Flow: L/hr (gal/hr)
M22x1,5 - 60°/Male
M12x1,5 - 60°/Male
5 (16)
see MTU fluids & lubrication spec.
600 (159)
l/hr
g/kwh
212
198
158
196
108
201
667 (176)
375 (21,326)
195 (11,089)
45 (2559)
130 (34)
66 (2329)
530 (986)
180 (6356)
8.5
➀ Represents standard product only.Consult Factory/MTU Onsite Energy distributor for additional configurations.
➁ Values in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
➂ Air density = 1.184 kg/m3 (0.0739 lbm/ft3)