DS0330D5S Datasheet, PDF (3/4 Pages) MTU Onsite Energy Corporation – DIESEl GENERATOR SET AIR CHARGE-AIR COOlING
3 / //  / 50 Hz 330 kVA
Standard Features➀
//  The generator set complies to G2
//  Engine-generator set tested to ISO 8528-5 for transient
response
//  Accepts rated load in one step per NFPA 110
//  All engine-generator sets are protoype and factory tested
//  MTU Onsite Energy is a single source supplier
//  Global product support
//  2 year standard warranty
//  Cooling system 50°C (integral set-mounted; engine driven
fan)
//  6R1600 diesel engine (10,5 liter displacement; common rail
fuel injection; 4-cycle)
//  Engine-generator resiliently mounted
//  Complete range of accessories
//  Brushless, rotating field generator (PMG excitation;
300% short circuit capability; 2/3 pitch stator windings)
//  Terminal box
Application data
//  Engine
Manufacturer
Model
Type
Arrangement
Displacement/cylinder: l (cu in)
Bore: mm (in)
Stroke: mm (in)
Compression ratio
Rated speed rpm
Engine governor
Max power: kWm (bhp)
Speed regulation
Air filter
MTU
6R1600G80F
4-Cycle
Inline 6
10.5 (641)
122 (4.8)
150 (5.91)
17.5:1
1500
ECU 8
301 (403)
±0.25%
Dry
//  Lube Oil Capacity
Total oil system: l (gal)
46 (12.2)
//  Electrical
Electric Volts DC
Cold cranking amps under -17.8°C (0°F)
24
1000
//  Fuel System
Fuel supply connection size➀
Fuel return connection size➀
Maximum fuel lift: m (ft)
Recommended fuel
Total fuel flow: l/hr (gal/hr)
24°Cone M22 x 1,5 - 60°/Male
24°Cone M16 x 1,5 - 60°/Male
5 (16)
see MTU fluids & lubrication spec.
171 (52.1)
//  Fuel Consumption
At 100% of power rating: l/hr (gal/hr)
At 75% of power rating: l/hr (gal/hr)
At 50% of power rating: l/hr (gal/hr)
Standby
72 (18.9)
53 (13.9)
36 (9.6)
//  Cooling/Radiator System
Ambient capacity of radiator: °C (°F)
Max. restriction of cooling air, intake,
and discharge side of rad.: kPa (in. H20)
Water pump capacity: l/min (gpm)
Heat rejection to coolant: kW (BTUM)
Heat rejection to after cooler: kW (BTUM)
Heat radiated to ambient: kW (BTUM)
Engine coolant capacity: l (gal)
Radiator coolant capacity: l (gal)
Coolant to cooler temperature: °C (°F)
Standby
50 (122)
0,2 (0,803)
277 (73,1)
155 (8,815)
65 (3,696)
14 (796)
45 (11,9)
44 (11,6)
95 (203)
//  Air Requirements➂
Standby
Aspirating: m3/min (SCFM) 24 (847.6)
Air flow required for rad.
cooled unit: m3/min (SCFM) 372 (13,137)
Remote cooled applications;
air flow required for dissipation
of radiated gen-set heat for a
max of 25°F rise: m3/min (SCFM) 110 (3,873)
//  Exhaust System
Gas temp. (stack): °C (°F)
Gas volume at stack
temp: m3/min (CFM)
Maximum allowable
back pressure: kPA (in. H20)
Standby
480 (896)
60 (2,118.9)
15 (60.2)
➀ Represents standard product only. Consult Factory/MTU Onsite Energy distributor for additional configurations.
➂ Air density = 1.184 kg/m3 (0.0739 lbm/ft3)