English
Language : 

300-XC6DT3 Datasheet, PDF (3/4 Pages) MTU Onsite Energy Corporation – DIESEL ENGINE-GENERATOR SET
3 / //  / 300-XC6DT3
Application data
//  Engine
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Max Power: Prime: bhp (kWm)
Regulation
Frequency
Air Cleaner
//  Liquid Capacity (Lubrication)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
//  Electrical
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
//  Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
//  Fuel Consumption
MTU Detriot Diesel
Series 60
(6063HV35)
4-Cycle
6-Inline
855 (14)
5.24 (13.3)
6.61 (16.8)
16:1
1,800
DDEC
490 (366)
424 (316)
±.25%
60 Hz
Dry
At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
STANDBY
25.4 (96)
20.2 (76)
13.7 (52)
//  Cooling - Radiator System
STANDBY
Ambient Capacity of Radiator: °F (°C) 122 (50)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H20 (kPa) 0.5 (0.12)
Water Pump Capacity: gpm (lit/min)
96 (363)
Heat Rejection to Coolant: BTUM (kW) 7,950 (140)
Heat Rejection to Air to Air: BTUM (kW) 5,150 (90)
Heat Radiated to Ambient: BTUM (kW) 5,276 (93)
PRIME
22.7 (86)
17.3 (66)
11.6 (44)
PRIME
122 (50)
0.5 (0.12)
96 (363)
7,000 (123)
4,750 (83)
4,930 (86.7)
9.5 (36)
6 (23)
42 (159)
24
950
1/2” NPT
1/2” NPT
6.7 (2.1)
Diesel #2
86.9 (329)
//  Air Requirements
Aspirating: *SCFM (m3/min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m3/min)
STANDBY
1,105 (31)
PRIME
1,070 (30)
18,891 (535) 18,891 (535)
11,899 (339) 11,118 (317)
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
//  Exhaust System
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m3/min)
Maximum Allowable
Back Pressure: in. H20 (kPa)
STANDBY
944 (507)
PRIME
871 (466)
2,903 (82) 2,657 (75)
40.8 (10.16) 40.8 (10.16)