3 / //  / 30-JC6DT4
Application data
//  Engine
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Max Power: Prime: bhp (kWm)
Regulation
Frequency
Air Cleaner
//  Liquid Capacity (Lubrication)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
//  Electrical
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
//  Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
//  Fuel Consumption
John Deere
4024TF281
4-Cycle
4 In-Line
149 (2.4)
3.4 (8.6)
4.1 (10.5)
20.5:1
1,800
Electric Isochronous
49 (36)
43 (32)
±1%
60 Hz
Dry
At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
STANDBY
2.8 (10.6)
2.1 (8)
1.4 (5.3)
//  Cooling - Radiator System
Ambient Capacity of Radiator: °F (°C)
Maximum Allowable Static
Pressure on Rad. Exhaust: in. H20 (kPa)
Water Pump Capacity: gpm (lit/min)
Heat Rejection to Coolant: BTUM (kW)
Heat Radiated to Ambient: BTUM (kW)
STANDBY
122 (50)
0.5 (0.12)
24 (91)
1,412 (25)
344 (6)
PRIME
2.5 (9.5)
1.9 (7.2)
1.2 (4.5)
PRIME
122 (50)
0.5 (0.12)
24 (91)
1,303 (23)
274 (4.8)
2.1 (8)
0.675 (2.6)
2.29 (8.7)
12
750
3/8” NPT
3/8” NPT
10 (3)
Diesel #2
26.4 (100)
//  Air Requirements
Aspirating: *SCFM (m3/min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m3/min)
STANDBY
106 (3)
PRIME
99 (2.8)
2,645 (75) 2,645 (75)
770 (22)
618 (18)
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
//  Exhaust System
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m3/min)
Maximum Allowable
Back Pressure: in. H20 (kPa)
STANDBY PRIME
1,026 (552) 963 (517)
283 (8)
261 (7.4)
30 (7.5)
30 (7.5)