MTU4R0113DS60 Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET | |||
|
DIESEL GENERATOR SET
MTU 4R0113 DS60
55 kWe /60 Hz /Prime
208 - 600V
Reference MTU 4R0113 DS60 (60 kWe) for Standby Rating Technical Data
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator
Model
Temp Rise
Connection
240V**
1
1
60
55
55
229
127
362CSL1604
105 °C/40 °C
12 LEAD
DOUBLE DELTA
240V**
1
1
60
55
55
229
130
361CSL1613
105 °C/40 °C
4 LEAD
** UL 2200 Oï¬ered
208V**
3
0.8
60
55
68
190
200
361CSL1602
105 °C/40 °C
12 LEAD WYE
240V**
3
0.8
60
55
68
165
200
361CSL1602
105 °C/40 °C
12 LEAD DELTA
380V**
3
0.8
60
55
68
104
172
361CSL1602
105 °C/40 °C
12 LEAD WYE
480V**
3
0.8
60
55
68
82
600V**
3
0.8
60
55
68
66
172
172
361CSL1601
105 °C/40 °C
12 LEAD WYE
361PSL1633
105 °C/40 °C
4 LEAD WYE
CERTIFICATIONS AND STANDARDS
//â Emissions â EPA Tier 3 Certiï¬ed
//â Generator set is designed and manufactured in
facilities certiï¬ed to standards ISO 9001:2008 and
ISO 14001:2004
//â Seismic Certification â Optional
â IBC Certiï¬cation
//â UL 2200 / CSA â Optional
â UL 2200 Listed
â CSA Certiï¬ed
//â Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Veriï¬ed product design, quality and performance integrity
- All engine systems are prototype and factory tested
//â Power Rating
- Accepts Rated Load in One Step Per NFPA 110
|
▷ |