English
Language : 

MTU3R0096DS30 Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET
DIESEL GENERATOR SET
MTU 3R0096 DS30
30 kWe /60 Hz /Standby
208 - 600V
Reference MTU 3R0096 DS30 (27 kWe) for Prime Rating Technical Data
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
240V**
1
1
60
30
30
125
65
285PSL1700
130 °C/40 °C
12 LEAD
DOUBLE DELTA
208V**
3
0.8
60
30
37
104
142
285PSL1700
130 °C/40 °C
12 LEAD WYE
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
240V**
3
0.8
60
30
37
90
142
285PSL1700
130 °C/40 °C
12 LEAD DELTA
380V**
3
0.8
60
30
37
57
187
285PSL1700
130 °C/40 °C
12 LEAD WYE
480V**
3
0.8
60
30
37
45
187
285PSL1700
130 °C/40 °C
12 LEAD WYE
600V**
3
0.8
60
30
37
36
142
284PSL5252
130 °C/40 °C
4 LEAD WYE
//  Emissions – EPA Tier 4 Interim Certified
//  Generator set is designed and manufactured in
facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//  Seismic Certification – Optional
– IBC Certification
//  Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//  Power Rating
- Accepts Rated Load in One Step Per NFPA 110
//  UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified