MTU20V4000DS3000 Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET
DIESEL GENERATOR SET
MTU 20V4000 DS3000
2800 kWe /60 Hz /Data Center Continuous Power
380 - 13.8kV
Reference: MTU 20V4000 DS3000 (3000 kWe) for Standby Rating Technical Data
MTU 20V4000 DS3000 (2800 kWe) for Prime Rating Technical Data
SYSTEM RATINGS
Data Center Continuous Power
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator
Model
Temp Rise
Connection
380V
3
0.8
60
2800
3500
5324
4000
1030FDL1110
130 °C/40 °C
6 LEAD WYE
480V*
3
0.8
60
2800
3500
4210
5400
1030FDL1108
130 °C/40 °C
6 LEAD WYE
* UL 2200 Offered
600V
3
0.8
60
2800
3500
3368
6125
1030FDS1126
130 °C/40 °C
6 LEAD WYE
4160V
3
0.8
60
2800
3500
486
5250
1020FDM1184
130 °C/40 °C
6 LEAD WYE
12470V
3
0.8
60
2800
3500
162
5125
1030FDH1254
130 °C/40 °C
6 LEAD WYE
13200V
3
0.8
60
2800
3500
153
13800V
3
0.8
60
2800
3500
146
5625
6000
1030FDH1254
130 °C/40 °C
6 LEAD WYE
1030FDH1254
130 °C/40 °C
6 LEAD WYE
CERTIFICATIONS AND STANDARDS
//  Emissions – EPA Tier 2 Certified
//  Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//  Seismic Certification – Optional
– IBC Certification
– OSHPD Pre-Approval
//  UL 2200 Listed – Optional
//  Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//  Power Rating
- Data Center Continuous Power (DCCP) rating is optimized
for data center applications
- Uptime Institute compliant for Tier III and IV data centers
- No runtime limitation
- 100% Load Factor
- 10% Overload Available
- Accepts Load in One Step Per NFPA 110