English
Language : 

MTU16V2000DS900 Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET
DIESEL GENERATOR SET
MTU 16V2000 DS900
900 kWe /60 Hz /Standby
208 - 4160V
Reference MTU 16V2000 DS900 (800 kWe) for Prime Rating Technical Data
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
208V**
3
0.8
60
900
1125
3123
2600
741RSL4045
130 °C/40 °C
12 LEAD LOW WYE
* Consult the factory for alternate configuration.
** UL 2200 Offered
240V**
3
0.8
60
900
1125
2706
380V
3
0.8
60
895
1118
1699
2600
741RSL4045
130 °C/40 °C
12 LEAD HI DELTA
1850
740RSL4046
130 °C/40 °C
4 BAR WYE
480V**
3
0.8
60
900
1125
1353
2500
574RSL4038
130 °C/40 °C
4 LEAD WYE
600V**
3
0.8
60
900
1125
1083
2850
574RSS4280
130 °C/40 °C
4 LEAD WYE
4160V
3
0.8
60
900
1125
156
1950
741FSM4360
130 °C/40 °C
6 LEAD WYE
CERTIFICATIONS AND STANDARDS
//  Emissions – EPA Tier 2 Certified
//  Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//  UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
//  Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//  Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 85%.