MTU12V4000DS1500 Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET | |||
|
DIESEL GENERATOR SET
MTU 12V4000 DS1500
1400 kWe /60 Hz /Data Center Continuous Power
380 - 4160V
Reference: MTU 12V4000 DS1500 (1500 kWe) for Standby Rating Technical Data
MTU 12V4000 DS1500 (1400 kWe) for Prime Rating Technical Data
SYSTEM RATINGS
Data Center Continuous Power
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
380V
3
0.8
60
1400
1750
2662
3350
744RSL4054
130 °C/40 °C
4 LEAD WYE
* Consult the factory for alternate conï¬guration.
** UL 2200 Oï¬ered
480V**
3
0.8
60
1400
1750
2105
3500
742RSL4050
130 °C/40 °C
4 LEAD WYE
600V**
3
0.8
60
1400
1750
1684
4800
743RSS4290
130 °C/40 °C
4 LEAD WYE
4160V
3
0.8
60
1400
1750
243
3900
743FSM4368
130 °C/40 °C
6 LEAD WYE
CERTIFICATIONS AND STANDARDS
//â Emissions â EPA Tier 2 Certiï¬ed
//â Generator set is designed and manufactured
in facilities certiï¬ed to standards ISO 9001:2008 and
ISO 14001:2004
//â Seismic Certification â Optional
â IBC Certiï¬cation
â OSHPD Pre-Approval
//â UL 2200 / CSA â Optional
â UL 2200 Listed
â CSA Certiï¬ed
//â Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Veriï¬ed product design, quality and performance integrity
- All engine systems are prototype and factory tested
//â Power Rating
- Data Center Continuous Power (DCCP) rating is optimized
for data center applications
- Uptime Institute compliant for Tier III and IV data centers
- No runtime limitation
- 100% Load Factor
- 10% Overload Available
- Accepts Load in One Step Per NFPA 110
|
▷ |