MTU12V1600DS715 Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET | |||
|
DIESEL GENERATOR SET
MTU 12V1600 DS715
715 kVA /50 Hz /Standby (Fuel-Optimized)
380 - 415V
Reference MTU 12V1600 DS715 (650 kVA Fuel and Exhaust-Optimized) for Prime Rating Technical Data
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
380V
3
0.8
50
572
715
1086
1450
573RSL4033
150 °C/40 °C
4 LEAD WYE
400V
3
0.8
50
572
715
1032
1600
573RSL4033
150 °C/40 °C
4 LEAD WYE
415V
3
0.8
50
572
715
995
2000
574RSL4037
150 °C/40 °C
4 LEAD WYE
CERTIFICATIONS AND STANDARDS
//â Generator set is designed and manufactured
in facilities certiï¬ed to standards ISO 9001:2008 and
ISO 14001:2004
//â Seismic Certification â Optional
â IBC Certiï¬cation
â OSHPD Pre-Approval
//â Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 85%.
//â Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Veriï¬ed product design, quality and performance integrity
- All engine systems are prototype and factory tested
|
▷ |