MTU12V1600DS600 Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET | |||
|
DIESEL GENERATOR SET
MTU 12V1600 DS600
600 kWe /60 Hz /Standby
208 - 600V
Reference MTU 12V1600 DS600 (550 kWe) for Prime Rating Technical Data
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
* UL 2200 Oï¬ered
208V*
3
0.8
60
600
750
2082
1200
573RSL4033
130 °C/40 °C
12 LEAD WYE
240V*
3
0.8
60
600
750
1804
1200
573RSL4033
130 °C/40 °C
12 LEAD DELTA
CERTIFICATIONS AND STANDARDS
380V
3
0.8
60
600
750
1140
1200
573RSL4035
130 °C/40 °C
12 LEAD WYE
440V
3
0.8
60
600
750
984
1400
573RSL4033
130 °C/40 °C
12 LEAD WYE
480V*
3
0.8
60
600
750
902
1430
572RSL4031
130 °C/40 °C
12 LEAD WYE
600V*
3
0.8
60
600
750
722
1430
572RSS4272
130 °C/40 °C
4 LEAD WYE
//â Emissions â EPA Tier 2 Certiï¬ed
//â Generator set is designed and manufactured
in facilities certiï¬ed to standards ISO 9001:2008 and
ISO 14001:2004
//â Seismic Certification â Optional
â IBC Certiï¬cation
â OSHPD Pre-Approval
//â Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Veriï¬ed product design, quality and performance integrity
- All engine systems are prototype and factory tested
//â Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 85%.
//â UL 2200 / CSA â Optional
â UL 2200 Listed
â CSA Certiï¬ed
|
▷ |