MTU12V1600DS550 Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL POWER MODULE
DIESEL POWER MODULE
MTU 12V1600 DS550
Voltages:
550 kWe /60 Hz /Prime - 208V, 480V
550 kWe /60 Hz /Prime - 600V
650 kVA /50 Hz /Prime - 400V
SYSTEM RATINGS
60 Hz
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
208V
3
0.8
60
550
688
1908
480V
3
0.8
60
550
688
827
1500
573RSL4035
105 °C/40 °C
12 LEAD LOW WYE
2120
573RSL4035
105 °C/40 °C
12 LEAD HI WYE
* Prime 50 Hz technical data is for a Fuel-Optimized Prime unit.
600V
3
0.8
60
550
668
662
2380
573RSS4276
105 °C/40 °C
4 LEAD WYE
50 Hz *
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
400V
3
0.8
50
520
650
938
1600
573RSL4035
105 °C/40 °C
12 LEAD HI WYE
CERTIFICATIONS AND STANDARDS
//  Emissions
– EPA Tier 2 Certified (60 Hz)
– Fuel Optimized (50 Hz)
//  Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//  Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//  Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 75%.