MTU10V1600DS450 Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET | |||
|
DIESEL GENERATOR SET
MTU 10V1600 DS450
400 kWe /60 Hz /Prime
208 - 600V
Reference MTU 10V1600 DS450 (450 kWe) for Standby Rating Technical Data
SYSTEM RATINGS
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
* UL 2200 Oï¬ered
208V*
3
0.8
60
400
500
1388
790
572RSL4025
105 °C/40 °C
12 LEAD WYE
240V*
3
0.8
60
400
500
1203
790
572RSL4025
105 °C/40 °C
12 LEAD DELTA
CERTIFICATIONS AND STANDARDS
380V
3
0.8
60
400
500
760
650
572RSL4025
105 °C/40 °C
12 LEAD WYE
440V
3
0.8
60
400
500
656
900
572RSL4025
105 °C/40 °C
12 LEAD WYE
480V*
3
0.8
60
400
500
601
1090
572RSL4025
105 °C/40 °C
12 LEAD WYE
600V*
3
0.8
60
400
500
481
1040
572RSS4270
105 °C/40 °C
4 LEAD WYE
//â Emissions â EPA Tier 3 Certiï¬ed
//â Generator set is designed and manufactured
in facilities certiï¬ed to standards ISO 9001:2008 and
ISO 14001:2004
//â Seismic Certification â Optional
â IBC Certiï¬cation
â OSHPD Pre-Approval
//â Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Veriï¬ed product design, quality and performance integrity
- All engine systems are prototype and factory tested
//â Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 75%.
//â UL 2200 / CSA â Optional
â UL 2200 Listed
â CSA Certiï¬ed
|
▷ |