GS400-6S Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – GAS GENERATOR SET | |||
|
GAS GENERATOR SET
GS400-6S
400 kWe /60 Hz /Standby
208 - 600V
(Reference GP355N6S for Prime Rating Technical Data)
SYSTEM RATINGS
Standby (NG)
Standby (LP)
GS400N6SGA
GS400L6SGA
Voltage (L-L)
Phase
PF
Hz
Natural Gas
Ratings: Amps
Natural Gas
Ratings: kW/kVA
LP Gas
Ratings: Amps
LP Gas
Ratings: kW/kVA
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V**
1
1.0
60
1604
385/385
1187
285/285
760
574RSL4037
130 °C/40 °C
12 LEAD ZIG-ZAG
* Consult the factory for alternate conï¬guration.
** UL 2200 Oï¬ered
GS400N6SPA
GS400L6SPA
208V**
3
0.8
60
GS400N6SJA
GS400L6SJA
240V**
3
0.8
60
1388
1203
400/500
400/500
1023
887
295/368
295/368
1500
572RSL4029
130 °C/40 °C
12 LEAD LOW WYE
1500
572RSL4029
130 °C/40 °C
12 LEAD HI DELTA
GS400N6SRA
GS400L6SRA
480V**
3
0.8
60
601
400/500
443
295/368
1500
572RSL4029
130 °C/40 °C
12 LEAD HI WYE
GS400N6SNA
GS400L6SNA
600V**
3
0.8
60
481
400/500
355
295/368
1080
433RSS4266
130 °C/40 °C
4 LEAD WYE
CERTIFICATIONS AND STANDARDS
//â Generator set is designed and manufactured
in facilities certiï¬ed to standards ISO 9001:2008 and
ISO 14001:2004
//â Power Rating
- Accepts Rated Load in One Step Per NFPA 110
//â UL 2200 / CSA â Optional
â UL 2200 Listed
â CSA Certiï¬ed
//â Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
- Veriï¬ed product design, quality and performance integrity
- All engine systems are prototype and factory tested
|
▷ |