GS350-6S Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – GAS GENERATOR SET | |||
|
GAS GENERATOR SET
GS350-6S
350 kWe /60 Hz /Standby
208 - 600V
(Reference GP300N6S for Prime Rating Technical Data)
SYSTEM RATINGS
Standby (NG)
Standby (LP)
GS350N6SGA
GS350L6SGA
Voltage (L-L)
Phase
PF
Hz
Natural Gas
Ratings: Amps
Natural Gas
Ratings: kW/kVA
LP Gas
Ratings: Amps
LP Gas
Ratings: kW/kVA
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V**
1
1.0
60
1438
345/345
1000
240/240
700
573RSL4035
130 °C/40 °C
12 LEAD ZIG-ZAG
* Consult the factory for alternate conï¬guration.
** UL 2200 Oï¬ered
GS350N6SPA
GS350L6SPA
208V**
3
0.8
60
1214
350/437
850
245/306
930
433CSL6216
130 °C/40 °C
12 LEAD LOW WYE
GS350N6SJA
GS350L6SJA
240V**
3
0.8
60
1052
350/437
737
245/306
930
433CSL6216
130 °C/40 °C
12 LEAD HI DELTA
GS350N6SRA
GS350L6SRA
480V**
3
0.8
60
526
350/437
368
245/306
1238
433CSL6216
130 °C/40 °C
12 LEAD HI WYE
GS350N6SNA
GS350L6SNA
600V**
3
0.8
60
481
350/437
295
245/306
1100
433PSL6248
130 °C/40 °C
4 LEAD WYE
CERTIFICATIONS AND STANDARDS
//â Generator set is designed and manufactured
in facilities certiï¬ed to standards ISO 9001:2008 and
ISO 14001:2004
//â UL 2200 / CSA â Optional
â UL 2200 Listed
â CSA Certiï¬ed
//â Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
- Veriï¬ed product design, quality and performance integrity
- All engine systems are prototype and factory tested
//â Power Rating
- Accepts Rated Load in One Step Per NFPA 110
|
▷ |