English
Language : 

GS125-6S Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – GAS GENERATOR SET
GAS GENERATOR SET
GS125-6S
125 kWe /60 Hz /Standby
208 - 600V
SYSTEM RATINGS
Standby (NG)
Standby (LP)
GS125N6SDA
GS125L6SDA
GS125N6SGA
GS125L6SGA
GS125N6SPA
GS125L6SPA
Voltage (L-L)
Phase
PF
Hz
Natural Gas
Ratings: Amps
Natural Gas
Ratings: kW/kVA
LP Gas
Ratings: Amps
LP Gas
Ratings: kW/kVA
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V**
1
1
60
521
125/125
521
125/125
196
431PSL6224
130 °C/40 °C
4 LEAD
240V**
1
1
60
521
125/125
521
125/125
130
431CSL6204
130 °C/40 °C
12 LEAD ZIG-ZAG
** UL 2200 Offered
Note: This unit is available with a dual fuel configuration.
208V**
3
0.8
60
434
125/156.25
434
125/156.25
323
363CSL1607
130 °C/40 °C
12 LEAD LOW WYE
GS125N6SJA
GS125L6SJA
GS125N6SRA
GS125L6SRA
240V**
3
0.8
60
480V**
3
0.8
60
376
188
125/156.25
125/156.25
376
188
125/156.25
125/156.25
323
363CSL1607
130 °C/40 °C
12 LEAD HI DELTA
430
363CSL1607
130 °C/40 °C
12 LEAD HI WYE
GS125N6SNA
GS125L6SNA
600V**
3
0.8
60
151
125/156.25
151
125/156.25
331
363PSL1658
130 °C/40 °C
4 LEAD WYE
CERTIFICATIONS AND STANDARDS
//  Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//  UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
//  Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//  Power Rating
- Accepts Rated Load in One Step Per NFPA 110