DS400D6S Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET | |||
|
DIESEL GENERATOR SET
DS400D6S
400 kWe /60 Hz /Standby
208 - 600V
(Reference DP365D6S for Prime Rating Technical Data)
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
** UL 2200 Oï¬ered
DS400D6SPA
208V**
3
0.8
60
400
500
1388
DS400D6SJA
240V**
3
0.8
60
400
500
1203
DS400D6SVA
380V
3
0.8
60
400
500
760
800
572RSL4025
130 °C/40 °C
12 LEAD LOW WYE
820
572RSL4025
130 °C/40 °C
12 LEAD HI DELTA
640
572RSL4025
130 °C/40 °C
12 LEAD HI WYE
CERTIFICATIONS AND STANDARDS
DS400D6SWA
440V
3
0.8
60
400
500
656
DS400D6SRA
480V**
3
0.8
60
400
500
601
920
433CSL6220
130 °C/40 °C
12 LEAD HI WYE
1277
433CSL6220
130 °C/40 °C
12 LEAD HI WYE
DS400D6SNA
600V**
3
0.8
60
400
500
481
1100
433PSL6248
130 °C/40 °C
4 LEAD WYE
//â Emissions â EPA Tier 3 Certiï¬ed
//â Generator set is designed and manufactured
in facilities certiï¬ed to standards ISO 9001:2008 and
ISO 14001:2004
//â Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
- Veriï¬ed product design, quality and performance integrity
- All engine systems are prototype and factory tested
//â UL 2200 / CSA â Optional
â UL 2200 Listed
â CSA Certiï¬ed
//â Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 85%.
|
▷ |